SG-DATADUMP Command

Purpose:

Report/Set fault record DATADUMP to COM1

Syntax:

SG-DATADUMP[={mode}] where mode is 0/1 (disabled/enabled)

Example:

SG-DATADUMP or SG-DATADUMP=1

Reference:

Section 6, Reporting and Alarms, Fault Reporting

SG-DI Command

Purpose:

Read/Set demand current interval

Syntax:

SG-DI[p][={interval}] where p=P/N/Q, interval=0-60 (min)

Example:

SG-DI or SG-DIP=15 or SG-DIN=1

Reference:

Section 6, Reporting and Alarms, Demand Functions

SG-DST Command

Purpose:

Read/Set Daylight Saving Time (DST) type

Syntax:

SG-DST[=1/2] where 1 means floating date, and 2 means fixed date

Example:

SG-DST, SG-DST=1, SG-DST=2

Reference: Section 6, Reporting and Alarms, Clock

SG-DSTSTART Command

Purpose:

Read/Set settings for start of Daylight Saving Time

Syntax:

SG-DSTSTART[={Mo,D,H,M,O}] where Mo=Month, D=Day of week (or month), H=Hour,

M=Min, O=# of occurrence of 'D' in the month]

Example:

SG-DSTSTART, SG-DSTSTART=3,1,2,0,1 (For 2AM Mar 1) or SG-

DSTSTART=4,0,2,15,2 (For 2:15AM on 2nd Sunday in April)

Reference: Section 6, Reporting and Alarms, Clock

SG-DSTSTOP Command

Purpose:

Read/Set settings for end of Daylight Saving Time

Syntax:

SG-DSTSTOP[={Mo,D,H,M,O}] where Mo=Month, D=Day of week (or month), H=Hour,

M=Min, O=# of occurrence of 'D' in the month]

Example:

SG-DSTSTOP, SG-DSTSTOP=11,21,3,15,1 (For 3:15AM Nov. 21) or SG-

DSTSTOP=11,2,23,20,1 (For 11:20AM on 1st Tue in Nov.)

Reference: Section 6, Reporting and Alarms, Clock

SG-FREQ Command

Purpose:

Read/Enter power system Frequency

Syntax:

SG-FREQ[={freq(HZ)}]

Example:

SG-FREQ=60 or SG-FREQ=50

Reference:

Section 3, Input and Output Functions, Current Inputs

SG-HOLD Command

Purpose:

Read/Program Output Hold operation

Syntax:

SG-HOLD[n][={1/0 hold ena}] where 1=TRUE, 0=FALSE

Example:

SG-HOLD or SG-HOLD1=1 or SG-HOLD2=0

Reference:

Section 3, Input and Output Functions, Outputs

SG-ID Command

Purpose:

Read/Set relay ID and station ID used in reports

Syntax:

SG-ID[={relayID(up to 30 char)},{StationID(up to 30 char)}]

Example:

SG-ID=448,SUBSTATION3 or SG-ID=BUS851, POWERPOINT_SUBSTATION

Reference:

Section 6, Reporting and Alarms, Relay Identifier Information



11-14

BE1-851 ASCII Command Interface

9289900990 Rev R