Terminal blocks, Settings, Preparing the relay for service – Basler Electric BE1-851 User Manual

Page 281: Communication connections, Front/rear rs-232 connectors, Terminal blocks -19, Settings -19, Preparing the relay for service -19, Communication connections -19, Front/rear rs-232 connectors -19

Advertising
background image

Terminal Blocks

There are two sizes of terminal blocks used on the H1 case design, the current circuit block and the input-

output blocks. The current circuit terminal block is the larger of the two types and uses 8/32 inch Phillips

head screws with lock washers. The input-output block is the smaller of the two types and uses 6/32 inch

slot or Phillips head screws with no washer. The S1 case design uses slotted 10-32 washerless "pan-

head" screws for current inputs. The input-output blocks are the same size as those incorporated in the

H1 design, and use 6/32-inch slot or Phillips head screws.
As stated, the current circuit terminal block on the H1 case uses 8/32 inch Phillips head screws with lock

washers. The lock washer is an integral part of the current circuit wiring system and should not be

removed. Without the lock washer, the 8/32-inch screw may bottom out, preventing a tight fit against the

lug (screw feels tight but lug may move under the screw head).
The maximum wire lug width accommodated by the current circuit terminal block on the H1 case is .344

inches (8.6 mm). The maximum wire lug width accommodated by the input-output block on the H1 and S1

case is 0.320 inches (8.1 mm). Current inputs on the S1 case are not limited by the barrier board terminal

block design.

NOTE

Except as noted, connections to the relay should be made with a minimum

wire size of #14 AWG.

Settings

The settings for your application need to be entered and confirmed prior to placing the relay in service.

Register settings such as breaker duty can be entered to match the current state of your system.

Preparing the Relay for Service

Basler microprocessor-based protection systems are similar in nature to a panel of electromechanical or

solid-state component relays. Both must be wired together with inputs and outputs, and have operating

settings applied. Logic settings determine which protection elements are electronically wired to the inputs

and outputs of the device. Operating settings determine the pickup thresholds and time delays.
The logic and operating settings should be tested by applying actual inputs and operating quantities and

verifying proper output response. For more details, refer to Section 13, Testing and Maintenance. All of

the following connections and functions should be verified during commissioning tests:

Proper connection and sensing of current and voltage signals

Input and output contact connections

I/O sensing versus virtual sensing

Settings validation

Proper operation of equipment (main or auxiliary)

Proper alarming (to SCADA) and/or targeting

Refer to Section 7, BESTlogic™ Programmable Logic, for information about customizing preprogrammed

logic and creating user-defined logic, and Section 8, Application, for information about the application of

preprogrammed logic schemes.

Communication Connections

Front/Rear RS-232 Connectors

Front and rear RS-232 connectors are DB-9 female DCE connectors. Connector pin numbers, functions,

names, and signal directions are shown in Table 12-2. Figures 12-21 through 12-23 provide RS-232 cable

connection diagrams.

9289900990 Rev R

BE1-851 Installation

12-19

Advertising