Reset timer (79rst), Maximum cycle timer (max cycle), Sequence controlled block (scb) – Basler Electric BE1-851 User Manual

Page 88: Reset timer (79rst) -32, Maximum cycle timer (max cycle) -32, Sequence controlled block (scb) -32, Table 4-16. operating settings for reclosing -32

Advertising
background image

At the top of the screen is a pull-down menu labeled Logic. This menu allows viewing of the BESTlogic

settings for each preprogrammed logic scheme. A custom logic scheme must be created and selected in

the Logic pull-down menu at the top of the screen before BESTlogic setting can be changed. See Section

7, BESTlogic Programmable Logic. To the right of the Logic pull-down menu is a pull-down menu labeled

Settings. The Settings menu is used to select the setting group that the element’s settings apply to.
Selecting the time units selects the time measurement that applies to all of the reclosing timers, Reset

timer, Max Cycle timer, and Reset Fail timer.
Using the pull-down menus and buttons, make the application appropriate settings to the reclosing

function.
Table 4-16 summarizes the operating settings for Reclosing.

Table 4-16. Operating Settings for Reclosing

Setting

Range

Increment

Default

Time

Delays

0.1 to 600 seconds

0.001 second (0 to 0.999 seconds)

0.1 second (1.0 to 9.9 seconds)

1 second (10 to 600 seconds)
0.1 cycles (6 to 36000 cycles)

791 = 0
792 = 0
793 = 0
794 = 0

79R = 10s

79F = 1s

79M = 60s

Step List

1. 79SCB TRUE during Reset and while timing to Reset after

Lockout.

2. 79SCB TRUE when 79C is TRUE for first reclose and

while timing to Reset after first reclose.

3. 79SCB TRUE when 79C is TRUE for second reclose and

while timing to Reset after second reclose.

4. 79SCB TRUE when 79C is TRUE for third reclose and

while timing to Reset after third reclose.

5. 79SCB TRUE when 79C is TRUE for fourth reclose and

while timing to Reset after fourth reclose.

0

Reset Timer (79RST)

The 79RST is TRUE when the recloser is in the reset position. This setting can be changed on the

Reclosing screen in BESTCOMS. See Figure 4-34.

Maximum Cycle Timer (MAX Cycle)

Max Cycle is the reclose maximum operation time. If a reclose operation is not completed before the

maximum operate time expires, the recloser goes to Lockout. This timer limits the total fault clearing and

restoration sequence to a definable period. The timer starts when the first trip command is issued from a

protective element of the relay. The Max Cycle timer stops when the recloser is reset. If the total reclosing

time between Reset states exceeds the maximum reclose cycle timer setting, the recloser will go Lockout.

If the WAIT input goes high during the Max Cycle timing sequence, Max Cycle timing will “pause” until the

WAIT input goes low. If not desired, the Max Cycle timer can be disabled by setting it at zero. This setting

can be changed on the Reclosing screen in BESTCOMS. See Figure 4-34.

Sequence Controlled Block (SCB)

The 79SCB output is TRUE when the breaker is closed, the 79 close output (79C) is TRUE, and the

reclose sequence step is enabled with a non-zero value in the S#-79SCB command. A 0 (zero) disables

the 79SCB output. This setting can be changed on the Reclosing screen in BESTCOMS. See Figure

4-34.
Figure 4-35 shows a logic timing diagram showing all possible sequence control blocks enabled (TRUE).

In Figure 4-36, 79RTD is the reclose reset time delay and 79#TD is the reclose time delay where # is the

reclose shot number.

4-32

BE1-851 Protection and Control

9289900990 Rev R