Table 4-19. BESTlogic Settings for Virtual Breaker Control Switch

Function

Range/Purpose

Default

Mode

0 = Disable, 1 = Enable

0

Example 1. Make the following BESTlogic settings to the Virtual Breaker Control 101 element. Figure

4-43 illustrates these settings.

Logic:

User

Mode:

Enable

Select Before Operate Control of Virtual Breaker Control Switch

The state of each virtual selector switch can be controlled at the HMI through Screen 2.2.1. Control is also

possible through the ASCII command interface by using the select-before-operate commands CS-101

(control select-virtual control switch) and CO-101 (control operate-virtual control switch). This cannot be

done using BESTCOMS. A state change takes place immediately without having to execute an EXIT –

SAVE settings command.
The virtual switch control commands require the use of select-before-operate logic. First, the command

must be selected using the CS-101 command. After the select command is entered, there is a 30 second

window during which the CO-101 control command will be accepted. The control selected and the

operation selected must match exactly or the operate command will be blocked. If the operate command

is blocked, an error message is output.

CS/CO Command Examples:

Example 1.

Read the current status of the virtual control switch.

>CO-101

C

The returned setting indicated that the switch is in the after-close state.

Example 2.

Trip the breaker by closing the trip output of the virtual control switch.

>CS-101=T

101=T SELECTED

>CO-101=T

101=T EXECUTED

Retrieving Breaker Control Switch Status from the Relay

The virtual control switch state (after-trip or after-close) can be determined through the ASCII command

interface by using the RG-STAT (reports general-status) command. This cannot be done using

BESTCOMS. See Section 6, Reporting and Alarms, General Status Reporting, for more information.
HMI Screen 2.2.1 provides switch control and also displays the current status of the virtual control

switches (after-trip or after-close). As the previous Example 1 demonstrated, the state of each virtual

selector switch can be determined using the CO-101 command in a read-only mode.