Output

Purpose

Description

Label

State Labels

True

False

VO11

Protective Trip

Expression.

TRUE when any 50 or 51

element times out.

PROT_TRIP

TRIP

NORMAL

BESTlogic Expression: VO11=50TPT+50TNT+50TQT+51PT+51NT+51QT

VO12

Protection Picked Up

Expression.

TRUE when any 50 or 51

element picks up.

PROT_PU

PU

NORMAL

BESTlogic Expression: VO12=50TPPU+50TNPU+50TQPU+51PPU+51NPU+51QPU

VO13

N/A

N/A

VO13

TRUE

FALSE

BESTlogic Expression: VO13=SG1

VO14

N/A

N/A

VO14

TRUE

FALSE

BESTlogic Expression: VO14=0

VO15

The relay is in test mode,

breaker failure is

disabled, and reclosing is

disabled.

TRUE if IN4 is de-energized or

if Virtual Switch 343 is closed.

TEST_MODE

TEST

NORMAL

BESTlogic Expression: VO15=/IN4+343