Mode 1, PU/DO (Pickup/Dropout Timer)

The output will change to logic TRUE if the INITIATE input expression is TRUE for the duration of

PICKUP time delay setting T1. See Figure 4-22. If the initiate expression toggles to FALSE before time

T1, the T1 timer is reset. Once the output of the timer toggles to TRUE, the INITIATE input expression

must be FALSE for the duration of DROPOUT time delay setting T2. If the INITIATE input expression

toggles to TRUE before time T2, the output stays TRUE and the T2 timer is reset.

Figure 4-22. Mode 1, PU/DO (Pickup/Dropout Timer)

Mode 2, One-Shot Nonretriggerable Timer

The one-shot nonretriggerable timer starts its timing sequence when the INITIATE input expression

changes from FALSE to TRUE. See Figure 4-23. The timer will time for DELAY time T1 and then the

output will toggle to TRUE for DURATION time T2. Additional initiate input expression changes of state

are ignored until the timing sequence has been completed. If the duration time (T2) is set to 0, this timer

will not function. The timer will return to FALSE if the BLOCK input becomes TRUE.

Figure 4-23. Mode 2, One-Shot Nonretriggerable Timer

Mode 3, One-Shot Retriggerable Timer

This mode of operation is similar to the one shot nonretriggerable mode, except that if a new FALSE-to-

TRUE transition occurs on the INITIATE input expression, the output is forced to logic FALSE and the

timing sequence is restarted. See Figure 4-24.

Figure 4-24. Mode 3, One-Shot Retriggerable Timer