Breaker monitor setting commands, General setting commands, Breaker monitor setting commands -13 – Basler Electric BE1-851 User Manual

Page 255: General setting commands -13

Advertising
background image

SA-MIN Command

Purpose:

Read/Set minor alarm setting mask

Syntax:

SA-MIN[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]

Example:

SA-MIN or SA-MIN=2/6/7/10/11

Reference:

Section 6, Reporting and Alarms, Alarms Function

SA-RESET Command

Purpose:

Read/Set Programmable Alarms Reset logic

Syntax:

SA-RESET[={rst alm logic}]

Example:

SA-RESET or SA-RESET=VO1

Reference:

Section 6, Reporting and Alarms, Alarms Function

Breaker Monitor Setting Commands

SB Command

Purpose:

Read all breaker settings

Syntax:

SB

Example:

SB

Reference:

Section 6, Reporting and Alarms, Breaker Monitoring

SB-DUTY Command

Purpose:

Read/Set Breaker Contact Duty where mode = 0/1/2 (disabled/I/I^2)

Syntax:

SB-DUTY[={mode},{dmax},{BLKBKR logic}]

Example:

SB-DUTY=1,60E3,IN5

Reference:

Section 6, Reporting and Alarms, Breaker Monitoring

SB-LOGIC Command

Purpose:

Read/Set Breaker Contact Logic

Syntax:

SB-LOGIC[={breaker close logic}]

Example:

SB-LOGIC=IN1 (IN1=52a) or SB-LOGIC=/IN2 (IN2=52b)

Reference:

Section 6, Reporting and Alarms, Breaker Monitoring

General Setting Commands

SG Command

Purpose:

Read all general settings

Syntax:

SG

Example:

SG

Reference:

Section 11, ASCII Command Interface, Settings (S) Command Descriptions

SG-CLK Command

Purpose:

Read/Program format of date and time display

Syntax:

SG-CLK[={date format(M/D)},{time format(12/24)},{dst enable(0/1)}]

Example:

SG-CLK=D,12,1 or SG-CLK=M,24,0

Reference:

Section 6, Reporting and Alarms, Clock

SG-COM Command

Purpose:

Read/Set serial communications protocol

Syntax:

SG-COM[#[={baud},A{addr},P{pglen},R{reply ack},X{XON ena}]]

Example:

SG-COM0=9600 or SG-COM1=9600,A0,P24,R1,X1

Reference:

Section 11, ASCII Command Interface, Settings (S) Command Descriptions, Configuring

the Serial Port Communication Protocol



9289900990 Rev R

BE1-851 ASCII Command Interface

11-13

Advertising