Introduction, Appendix b • command cross-reference – Basler Electric BE1-851 User Manual

Page 353

Advertising
background image

APPENDIX B • COMMAND CROSS-REFERENCE

Introduction

This appendix lists all ASCII commands, command syntax, brief command descriptions, and any

corresponding HMI screens. Commands are organized by function in the following groups and tables:

Miscellaneous (Table B-1)

Metering (Table B-2)

Control (Table B-3)

Report (Table B-4)

Setting (Table B-5)

Alarm (Table B-6)

General Setting (Table B-7)

Breaker Monitor and Setting (Table B-8)

Programmable Logic Setting (Table B-9)

User Programmable Name Setting (Table B-10)

Protection Setting (Table B-11)

Global (Table B-12)

An entry of x in the HMI Screen column represents multiple entry possibilities such as 0, 1, 2, or 3 for

setting groups and 43, 143, 243, or 343 for virtual switches.

Table B-1. Miscellaneous Commands

ASCII Command

Function

HMI Screen

ACCESS[={password}]

Read/Set access level in order to change

settings.

N/A

EXIT

Exit programming mode.

N/A

HELP {cmd} or H {cmd}

Obtain help with command operation.

N/A

Table B-2. Metering Commands

ASCII Command

Function

HMI Screen

M

Read all metered values.

N/A

M-I[{phase}]

Read metered current in primary unit.

3.1 - 3.2

Table B-3. Control Commands

ASCII Command

Function

HMI Screen

CO-{control}[={mode}]

Control operation.

N/A

CS-control[={mode}]

Control selection.

N/A

CS/CO-x43

Control virtual switches.

2.1.1 - 2.1.4

CS/CO-101

Control breaker control switch.

2.2.1

CS/CO-GROUP

Control group.

2.3.1

CS/CO-OUTn

Control output n.

2.4.1

Table B-4. Report Commands

ASCII Command

Function

HMI Screen

RA[=0]

Report/Reset alarm information.

1.3

RA-LGC[=0]

Report/Reset logic alarm information.

N/A

RA-MAJ[=0]

Report/Reset major alarm information.

N/A

RA-MIN[=0]

Report/Reset minor alarm information.

N/A

RA-REL[=0]

Report/Reset relay alarm information.

N/A

RB

Read breaker status.

4.3.1 - 4.3.2

RB-DUTY[{phase}[={%duty}]]

Read/Set breaker contact duty log.

4.3.2

9289900990 Rev R

BE1-851 Command Cross-Reference

B-1

Advertising