An alarm variable is provided in the programmable alarms function that can be used to indicate an alarm

condition when the breaker failure protection trips. See Section 6, Reporting and Alarms, Alarms

Function, for more details on the alarm reporting function.

BESTlogic™ Settings for Breaker Failure Protection

BESTlogic settings are made from the BESTlogic Function Element screen in BESTCOMS. Figure 4-19

illustrates the BESTCOMS screen used to select BESTlogic settings for the breaker failure element. To

open the BESTlogic Function Element screen for Breaker Failure, select Breaker Failure from the

Screens pull-down menu. Then select the BESTlogic button. Alternately, settings may be made using the

SL-BF ASCII command.

Figure 4-19. BESTlogic Function Element Screen, Breaker Failure


At the top center of the BESTlogic Function Element screen is a pull-down menu labeled Logic. This

menu allows viewing of the BESTlogic settings for each preprogrammed logic scheme. User or custom

logic must be selected on this menu in order to allow changes to the mode and inputs of the

function/element.
Enable the setting group control function by selecting its mode of operation from the Mode pull-down

menu. To connect the elements inputs, select the button for the corresponding input in the BESTlogic

Function Element screen. The BESTlogic Expression Builder screen will open. Select the expression type

to be used. Then, select the BESTlogic variable or series of variables to be connected to the input. Select

Save when finished to return to the BESTlogic Function Element screen. These settings will enable the

function block by attaching it to one of the CT input circuits and provide initiate and blocking control as

determined by the logic expressions assigned to those inputs. For details on the BESTlogic Expression

Builder, see Section 7, BESTlogic Programmable Logic. Select Done when the settings have been

completely edited.
Table 4-11 summarizes the BESTlogic settings for Breaker Failure Protection.

Table 4-11. BESTlogic Settings for Breaker Failure Protection

Setting

Range/Purpose

Default

Mode

0 = Disabled, 1 = Enabled

0

Initiate

Logic expression that enables function when TRUE.

0

Block

Logic expression that disables function when TRUE.

0

9289900990 Rev R

BE1-851 Protection and Control