Time overcurrent characteristic curves – Basler Electric BE1-851 User Manual

Page 332

Advertising
background image

Table A-1. 51P, 51N, and 51Q Time Characteristic Curve Constants

Curve

Selection

Curve Name

Trip Characteristic Constants

Reset †

A

B

C

N

K

R

S1

Short Inverse

0.2663 0.03393

1

1.2969

0.028

0.5

S2

Short Inverse

0.0286

0.0208

1

0.9844

0.028

0.094

L1

Long Inverse

5.6143 2.18592

1

1

0.028

15.75

L2

Long Inverse

2.3955

0

1

0.3125

0.028

7.8001

D

Definite Time

0.4797 0.21359

1

1.5625

0.028

0.875

M

Moderately Inverse

0.3022

0.1284

1

0.5

0.028

1.75

I1

Inverse Time

8.9341 0.17966

1

2.0938

0.028

9

I2

Inverse Time

0.2747 0.10426

1

0.4375

0.028

0.8868

V1

Very Inverse

5.4678 0.10814

1

2.0469

0.028

5.5

V2

Very Inverse

4.4309

0.0991

1

1.9531

0.028

5.8231

E1

Extremely Inverse

7.7624 0.02758

1

2.0938

0.028

7.75

E2

Extremely Inverse

4.9883

0.0129

1

2.0469

0.028

4.7742

A

Standard Inverse

0.01414

0

1

0.02

0.028

2

B

Very Inverse (I

2

t)

1.4636

0

1

1.0469

0.028

3.25

C

Extremely Inverse (I

2

t)

8.2506

0

1

2.0469

0.028

8

G

Long Time Inverse (I

2

t)

12.1212

0

1

1

0.028

29

F

Fixed Time ∗

0

1

0

0

0.028

1

P

Programmable ‡

0 to 600 0 to 25

0 to 1

0.5 to 2.5

0.028

0 to 30


∗

Curve F has a fixed delay of one second times the Time Dial setting.

† For integrated reset, append

R to the curve name. For example, curve S1 has instantaneous reset.

Curve

S1R has integrated reset.

‡ The programmable curve allows for four significant digits after the decimal place for every variable.

Time Overcurrent Characteristic Curves

Figures A-1 through A-16 illustrate the characteristic curves of the BE1-851 relay. Table A-2 cross-

references each curve to existing electromechanical relay characteristics. Equivalent time dial settings

were calculated at a value of five times pickup.

A-2

BE1-851 Time Overcurrent Characteristic Curves

9289900990 Rev R