BESTCOMS™ Software

BESTCOMS is a Windows® based graphical user interface (GUI) that runs on IBM-compatible computers.

The software is used to create settings files for protection, control, operating logic, breaker monitoring,

metering, and fault recording functionality. A primary advantage to BESTCOMS is that these setting files

may be created while off line (not connected to a unit). This feature gives the engineer flexibility in

developing, testing, and replicating the settings before exporting them to a file and transmitting the file to

technical personnel in the field.
The BESTCOMS GUI also includes the same preprogrammed logic schemes that are contained in the

relay. This allows engineers the flexibility of developing setting files using a preprogrammed logic

scheme, customizing a preprogrammed logic scheme or building a scheme from scratch. Logic schemes

are developed using the GUI Logic Builder. The logic builder uses basic Boolean and/or constructs to

develop logic schemes.

Primary Applications

The BE1-851 Overcurrent Protection System provides complete circuit protection with multiple

overcurrent elements and is intended for use in any non-directional overcurrent application. Its unique

capabilities make it ideally suited for applications where:

Low burden is required to extend the linear range of CTs.

One relay provides the flexibility of wide settings ranges, multiple settings groups, and multiple

coordination curves.

A multifunction, multi-phase relay is desired for economical and space saving benefits. A single

BE1-851 provides all of the protection, local and remote indication, metering, and control required

on a typical circuit.

Communication capability and protocol support is desired.

Applications that require specific current response characteristics.

o The fundamental digital signal-processing (DSP) algorithm provides rejection of

harmonics and low transient overreach.

o The RMS DSP algorithm provides true wide band RMS measurement.
o The average DSP algorithm provides a flat response characteristic over a wide frequency

range.

Bus protection is provided by a high-speed overcurrent-blocking scheme on the transformer bus

mains instead of a bus differential circuit.

The capabilities of intelligent electronic devices (IEDs) are used to decrease relay and equipment

maintenance costs.

Applications where the optional case configurations facilitate retrofit in existing substations. One

electromechanical overcurrent or reclosing relay can be replaced by a BE1-851 relay. The

remaining relays can be removed or left in service as backup.

Applications where the capabilities of a digital multifunction relay are required yet test paddles

and/or drawout construction is also required.