Operating settings for setting group control, Operating settings for setting group control -5, Figure 4-4. input control binary inputs -5 – Basler Electric BE1-851 User Manual

Page 61: Figure 4-5. setting group selection screen -5, Figure 4-4

Advertising
background image

Figure 4-4. Input Control Binary Inputs

Example 1. Make the following settings changes to the setting group control function. Set the setting

group control such that automatic selection is overridden and emergency overload

settings (SG3) are in place when transformer 2 is out of service. Contact Sensing Input 2

is TRUE when either the high side or low side breakers for Transformer 2 are open. Refer

to Figure 4-2 for an example.

Mode:

Binary Inputs

D0:

Connect to IN2

D1:

Connect to IN2

D2:

Connect to 0

D3:

Connect to 0

Automatic:

Connected to /IN2

Operating Settings for Setting Group Control

Operating settings can be made using BESTCOMS. Figure 4-5 illustrates the BESTCOMS screen used to

select operational settings for the Setting Group Control function. To open the Setting Group Selection

screen, select Setting Group Selection from the Screens pull-down menu. Alternately, settings can be

made from the ASCII command interface using the SG-SGCON (settings general-SGC Alarm on time)

command.

Figure 4-5. Setting Group Selection Screen

9289900990 Rev R

BE1-851 Protection and Control