Table 8-2. Factory Default Function Blocks Logic Settings

Function

Purpose

BESTlogic

Expression

Mode

Setting

50TP

Used for instantaneous phase overcurrent protection.

0

1 (enabled)

50TN

Used for instantaneous neutral overcurrent protection.

0

1 (enabled)

50TQ

Used for instantaneous negative-sequence overcurrent

protection.

0

1 (enabled)

150TP

N/A

0

1 (enabled)

150TN

N/A

0

1 (enabled)

150TQ

N/A

0

1 (enabled)

51P

Used for timed phase overcurrent protection.

0

1 (enabled)

51N

Used for timed neutral overcurrent protection.

0

1 (enabled)

51Q

Used for timed negative-sequence overcurrent protection.

0

1 (enabled)

62

N/A

0

0 (disabled)

162

N/A

0

0 (disabled)

79

N/A

0

0 (disabled)

BF

N/A

0

0 (disabled)

GROUP

Input 0 Logic: No manual selection logic is used.

0

1 (discrete

input

selection)

Input 1 Logic: No manual selection logic is used.

0

Input 2 Logic: No manual selection logic is used.

0

Input 3 Logic: No manual selection logic is used.

0

Auto/Manual Logic: Set to 1 (/0) to enable automatic

selection. No manual selection is used.

/0

Table 8-3. Factory Default Virtual Switch Logic Settings

Switch

Purpose

Mode

Label

State Labels

True

False

43

N/A

1 (Off/On/Pulse)

SWITCH_43

TRUE

FALSE

143

N/A

1 (Off/On/Pulse)

SWITCH_143

TRUE

FALSE

243

N/A

1 (Off/On/Pulse)

SWITCH_243

TRUE

FALSE

343

N/A

1 (Off/On/Pulse)

SWITCH_343

TRUE

FALSE

101

Virtual Control Switch to

trip bus breaker.

1 (enable)

N/A

N/A

N/A

8-4

BE1-851 Application

9289900990 Rev R