3. PT-LINK CONFIGURATION

PT-Link II BACnet3 Interface

14

3.4 Changing the Confi g.csv File

7.)

Inside the text fi le under ‘Connections’, change the ‘Server_DIP’

parameter from ‘Enabled’ to ‘Disabled’. (See Figure 17).

5.) Near the top of

the text fi le under ‘System_Node_ID’, change the

BACnet MAC address from the default of 11 (Figure 15). You can
obtain this address to enter from your Building Automation System
(BAS) Integrator.

Figure 15: System Node ID

Figure 17: Server Dip Switch

6.)

If you need to change the server baud rate, under ‘Connections’,

change the Server_Baud (Figure 16). Possible Baud Rate values are
(9600, 19200, 38400, and 76800). The default Baud Rate is 38400. You
can obtain the correct baud rate from your BAS Integrator.

Figure 16: Server Baud Rate

8.)

The last change you may need to make is the Node_ID under ‘Client

Side Nodes’ which is the BACnet Device Instance Number (Figure 18).
The default is 1.You can obtain the Node ID from your BAS Integrator.

Figure 18: Client Node ID

9.)

Once all changes have been made to the text fi le, while still in

Notepad, click

<File>

in the upper left and then click

<Save>

. Now

close the fi le and return

to the FS-GUI Screen open in your browser.

NOTE: Do not rename the fi le. The fi le must always be named

confi g.csv”; otherwise, it will be ignored by the PT-
Link.