7. PARAMETER TABLES

PT-Link II BACnet3 Interface

36

7.1 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Force

HVAC

Mode

FrcHvacM

AV: 262

Overrides

normal controller

operation in

order to force

the unit into this

desired mode.

Confi guring

for “Auto” will

restore normal

unit control of

the mode of

operation.

0=Auto

1=Vent

2=Cool
3=Heat

4=Vent

Dehum.

5=Cool

Dehum.

6=Heat

Dehum.

Head

Pressure

HeadPr

AI:276

Current value of

the Head

Pressure

Reading.

Head

Pressure
Setpoint

HeadPrSt

AI:279

Current Head

Pressure

Setpoint.

Head

Pressure
Setpoint

in Cooling

Mode

ClHdPrSt

AV:293

This is the Head

Pressure Setpoint

the unit will

control to in the

Cooling Mode.

240

PSI

420

PSI

Head

Pressure
Setpoint

in Reheat

Mode

HtHdPrSt

AV:294

This is the Head

Pressure Setpoint

the unit will

control to in the

Dehumidifi cation

Reheat Mode.

240

PSI

420

PSI

High Head

Pressure

HiHedPr

BI: 381

Indicates the

Head Pressure is

too high.

SAT

Heating

Low Reset

Source

HtLoRt

AV: 328

If doing Supply

Air Setpoint

Reset, this is

the Low Reset

Source value in

Heating that will

correspond to the

Supply Air Heat-

ing High Reset

Setpoint.

1

150

SAT

Heating

High Reset

Source

HtHiRt

AV: 329

If doing Supply

Air Setpoint

Reset, this is

the High Reset

Source value in

Cooling that will

correspond to

the Supply Air

Cooling Setpoint

(Low Reset).

1

150

Heating

Enabled

HtEnbl

AI: 30

Status that

indicates that

mechanical heat-

ing is enabled to

operate.

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Heating

Setpoint

Mirror

HtSt

AI: 31

Occupied

Heating Mode

Enable Setpoint.

Heat

Staging

Window

HtStgWdw

AV: 341

In the Heat-

ing Mode, if

the Supply Air

Temperature

rises above the

Active Supply

Air Heating

Setpoint plus the

Heating Stage

Off Window

value, a Heating

stage will be

deactivated after

its Minimum

Run Time.

1

50

Mechani-

cal Heating

Lockout

MchHtLkt

AV: 343

The VCB-X

will Lockout

Mechanical

Heating when

the Outdoor Air

Temperature
is above this

Setpoint.

-30

150

Mechani-

cal Heating

Alarm

MchHtAlm

BI: 95

Heating Mode

has been initiated

but the Supply

Air Temperature

has not risen

5°F within a

user-adjustable

time period. This

does not apply

for Modulating

Heating.

Heat Pump

Compres-

sor Heating

Outdoor
Lockout

HpLkt

AV: 351

Compressor

Heating will be

locked out when

the Outdoor Air

Temperature
is below this

Setpoint.

-30

100

Heat Pump

Defrost

Interval

HpDfrInt

AV: 355

The Heat Pump

Defrost Interval

is the length of

time that must

be met between
Defrost Modes.

10

Min

120

Min

Heat

Wheel

Defrost

Setpoint

Dfrst

AV: 346

The unit will go

into Heat Wheel

Defrost Mode

when the Out-

door Air is below

this setpoint.

0

50

Indoor

Humidity

InRh

AI: 67

Current value

of the Indoor

Humidity

Sensor.