7. PARAMETER TABLES

PT-Link II BACnet3 Interface

46

BACnet Properties for VCM-X WSHP (Tulsa)

and RNE Controllers

Parameter

Name

Object

Description

Limits

Compressor 4

Lockout Alarm

B2LktAlm

BI: 229

Alarm that

indicates

Compressor B2

is locked out.

Low Water

Temperature 1

Alarm

LWT1Alm

BI: 230

Alarm that

indicates water

temperature is

below the

Leaving Water

Safety Setpoint

(Heating only)

for System A.

Low Water

Temperature 2

Alarm

LWT2Alm

BI: 231

Alarm that

indicates water

temperature is

below the

Leaving Water

Safety Setpoint

(Heating only)

for System B

Proof of Water 1

Flow Alarm

POWF1Alm

BI: 232

Alarm that

indicates no

Proof of Water

Flow for System

A (A1/A2)

Proof of Water 2

Flow Alarm

POWF2Alm

BI: 233

Alarm that

indicates no

Proof of Water

Flow for System

B (B1/B2)

Module

Communica-

tions Alarm

ComMAlm

BI: 234

Alarm that

indicates that one

or more Modules

are not

communicating

with the VCM-X

WSHP Control-

ler.

Bad Return Air

Sensor

RaTpAlm

BI: 365

Alarm that

indicates

a failure in the

Return Air Sen-

sor.

Title 24 Econo-

mizer Feedback

T24EcFb

AI: 384

Current position

of feedback from

Economizer

actuator.

7.3 VCM-X WSHP Tulsa & RNE BACnet Parameters

BACnet Properties for VCM-X WSHP (Tulsa)

and RNE Controllers

Parameter

Name

Object

Description

Limits

Title 24

Sensor Alarm

T24TpAlm

BI: 385

Outside Air

or Supply Air

Temperature

Sensor is shorted

or missing.

Title 24 Not

Economizing

When It Should

T24NEWS

BI: 386

Economizer is

enabled but not

following the

desired Econo-

mizer position

commanded.

Title 24 Econo-
mizing When It

Should Not

T24EWISN

BI: 387

Economizer is

not enabled but

the feedback

signal indicates
a position more

open than the

minimum.

Title 24 Damper

Failure

T24DpAlm

BI: 388

Economizer is

enabled but not

within 10% of

desired position

within 150

seconds.

Title 24 Excess

Outdoor Air

T24ExsOA

BI: 389

Economizer

feedback is lost

or Economizer

is not follow-

ing commanded

position.