Parameter tables, 3 vcm-x wshp (tulsa) & rne bacnet parameters, Pt-link ii bacnet3 interface – Orion System PT-Link II BACnet3 User Manual

Page 45

Advertising
background image

PT-Link II BACnet3 Interface

7. PARAMETER TABLES

45

7.3 VCM-X WSHP (Tulsa) & RNE BACnet Parameters

BACnet Properties for VCM-X WSHP (Tulsa)

and RNE Controllers

Parameter

Name

Object

Description

Limits

Remote VFD

Reset

RmVFDPos

AV:
258

Remote VFD

Position Reset

-1

100

Title 24 Econo-

mizer Alarms

AlmGrp5

AI: 391

Alarms for the 24

Title Economizer

Compressor A1

Low Suction

Pressure Alarm

A1LSPAlm

BI: 222

Alarm that

indicates

Suction Pressure

for Compressor
A1 is below the

Low Suction

Pressure

Cooling (Heat-

ing) Setpoint.

Compressor A1

Lockout Alarm

A1LktAlm

BI: 223

Alarm that

indicates

Compressor A1

is locked out.

Compressor A2

Low Suction

Pressure Alarm

A2LSPAlm

BI: 224

Alarm that

indicates

Suction Pressure

for Compressor
A2 is below the

Low Suction

Pressure Cool-

ing (Heating)

Setpoint.

Compressor A2

Lockout Alarm

A2LktAlm

BI: 225

Alarm that

indicates

Compressor A2

is locked out.

Compressor B1

Low Suction

Pressure Alarm

B1LSPAlm

BI: 226

Alarm that

indicates

Suction Pressure

for Compressor
B1 is below the

Low Suction

Pressure Cool-

ing (Heating)

Setpoint.

Compressor B1

Lockout Alarm

B1LktAlm

BI: 227

Alarm that

indicates

Compressor B1

is locked out.

Compressor B2

Low Suction

Pressure Alarm

B2LSPAlm

BI: 228

Alarm that

indicates

Suction Pressure

for Compressor
B2 is below the

Low Suction

Pressure Cool-

ing (Heating)

Setpoint.

BACnet Properties for VCM-X WSHP (Tulsa)

and RNE Controllers

Parameter

Name

Object

Description

Limits

Modulating

Compressor 2

MdCmp2

AI: 206

Current position

of the

2nd Stage of

Compressor

Modulation.

Head Pressure

Signal 1 on

Head Pressure

Module 1

HdPr1

AI: 207

Head Pressure

Signal 1 on

Head Pressure

Module 1

Head Pressure

Signal 2 on

Head Pressure

Module 1

HdPr2

AI: 208

Head Pressure

Signal 2 on

Head Pressure

Module 1

Condenser Fan

Signal 1 On

Head Pressure

Module 1

CdFan1

AI: 209

Condenser Fan

Signal 1 On

Head Pressure

Module 1

Condenser Fan

Signal 2 On

Head Pressure

Module 1

CdFan2

AI: 210

Condenser Fan

Signal 2 On

Head Pressure

Module 1

Water Temp. A

WaterTpA

AI: 220

Current water

temperature of

refrigerant for

System A.

Water Temp. B

WaterTpB

AI: 221

Current water

temperature of

refrigerant for

System B.

Condenser Fan

Signal 1 On

Head Pressure

Module 2

CdFan21

AI: 392

Condenser Fan

Signal 1 On

Head Pressure

Module 2

Condenser Fan

Signal 2 On

Head Pressure

Module 2

CdFan22

AI: 393

Condenser Fan

Signal 2 On

Head Pressure

Module 2

Head Pressure

Signal 1 on

Head Pressure

Module 2

HdPr21

AI: 394

Head Pressure

Signal 1 on

Head Pressure

Module 2

Head Pressure

Signal 2 on

Head Pressure

Module 2

HdPr22

AI: 395

Head Pressure

Signal 2 on

Head Pressure

Module 2

Advertising
This manual is related to the following products: