7. PARAMETER TABLES

PT-Link II BACnet3 Interface

38

7.1 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Minimum

Desired

Outdoor

Air CFM

OACfmMin

AV:291

Minimum Out-

door Airfl ow

CFM Setpoint

.10K

200K

Missing

Outdoor

Air CFM

Sensor

OaCfmAlm

BI: 370

Indicates

Outdoor Air

CFM Sensor is

not detected.

Outdoor

Humidity

OaRh

AI:52

Current value

of the Outdoor

Humidity

Sensor.

Outdoor

Air

Dewpoint

OaDewPt

AI: 332

Current calcu-

lated Outdoor

Air Dewpoint.

Outdoor

Air Tem-

perature

OaTp

AI: 54

Current value

of the

outdoor

temperature

sensor.

Outdoor

Air

Tempera-

ture Offset

OaTpOst

AV: 53

If the Outdoor

Temperature

Sensor is reading

incorrectly, use

this to enter an
offset to adjust

the Sensor’s

Temperature.

-100

100

Minimum

Outside

Air CFM

Deadband

OacfmDb

AV: 359

The Deadband

is used both

above and below

the Outdoor Air

CFM setpoint

to help prevent

hunting.

10

1000

Outdoor

Air Tem-

perature

Sensor

Lost

OaTpAlm

BI: 117

Indicates a

failure of the

Outdoor Air

Temperature

Sensor.

Outdoor
Wetbulb

OaWtbl

AI: 55

Current calcu-

lated value of the

outdoor wetbulb

temperature.

Preheat

Relay

Setpoint

PreHtAmb

AV:286

If the Supply Fan

is energized this

is the tempera-

ture at which the

Preheat Relay

will activate.

Operates only

in the Occupied

Mode.

-30

70

Proof

of Flow

Alarm

PofAlm

BI: 26

Indicates no

Proof of Water

Flow.

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Reheat

Enabled

RehtEnbl

BI: 363

Modulating

Hotgas Reheat

Enabled.

Reheat

Valve

Position

RtVlvPos

AI:277

Current position

of MHGRV

modulating hot

gas reheat valve.

Missing

Reheat

Module

MisMH-

GRV

BI: 374

Indicates that the

MHGRV Module

is not

communicating

with the VCB-X

Controller.

Return Air

CFM

RaCFM

AI:275

Current Return

Airfl ow

Measurement.

Missing

Return

Air CFM

Sensor

RaCfmSr

BI: 373

Indicates

that the Return

Air CFM Sensor

is not detected.

Return Air

Damper
Position

RaDmp

AI: 336

Current Return

Air Damper

position.

Return Air

Humidity

RaRH

AI: 337

Current value of

the Return Air

Humidity Sensor.

Return Air

Tempera-

ture

RaTp

AI: 64

Current value of

the return tem-

perature sensor.

Return Air

Tempera-

ture Sensor

Offset

RaTpOst

AV: 65

If the Return

Temperature

Sensor is reading

incorrectly, use

this to enter an
offset to adjust

the Sensor’s

Temperature.

-100

100

Bad Return

Air Sensor

RaTpAlm

BI: 365

Indicates a failure

of the Return Air

Sensor.

Return

Bypass

Damper
Position

RetBydmp

AI: 335

Current Return

Bypass Damper

position.

Schedule

Force

SchdFrc

AV: 66

0 = Auto (uses

controller’s

schedule)

1 = Forced

Occupied

2 = Forced

Unoccupied

0

2

Current

Slide

Adjust

Offset

SldAdOfs

AI: 338

Current Slide
Adjust Offset

value.