Parameter tables, 1 vcb-x bacnet parameters, Pt-link ii bacnet3 interface 32 – Orion System PT-Link II BACnet3 User Manual

Page 32: Zone

Advertising
background image

Zone

Zone

7. PARAMETER TABLES

PT-Link II BACnet3 Interface

32

7.1 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Bad or

Missing 12

Relay

Expansion

Board.

Mis12Rly

BI: 376

The 12 Relay

Expansion Board

is confi gured but

not detected.

Alarm

Group 1

AlmGrp1

AI: 104

See Alarm

Group Bits on

page 43.

Alarm

Group 2

AlmGrp2

AI: 105

See Alarm

Group Bits on

page 43.

Alarm

Group 3

AlmGrp3

AI: 106

See Alarm

Group Bits on

page 43.

Alarm

Status

AlmSts

AI: 1

Indicates that

there is an alarm.

0 = Off

1 = On

See Alarm

Group Bits on

page 43.

Appli-

cation

Software

Version

AppVer

AI: 99

Current version

of the software

in the unit.

Unit Mode

UnitMode

AI:123

See Unit Mode

Bits on page

43.

Building

Pressure

BuildPr

AI:272

Current value of

the Building

Pressure Sensor.

Building

Pressure
Setpoint

RfPrSt

AV:118

Current Building

Pressure

Setpoint.

-.20

.20

Building

Pressure

Control

Deadband

RfPrDb

AV:358

Value above

and below the

Building Pres-

sure Setpoint

where no control

change occurs.

.01

0.1

CO

2

CO2

AI:271

Current CO

2

Level.

CO

2

Sensor

Calibration

Deadband

Offset

CO2Ost

AV: 348

If the CO

2

Sensor is reading

incorrectly, you

can use this

option to enter
an offset value

to adjust the

Sensor’s CO

2

reading.

-500

ppm

500

ppm

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

CO

2

Minimum

Setpoint

CO2MinLv

AV:287

This is the

threshold CO

2

level at which

the Economizer

Min Damper

Position

Setpoint will

begin to be reset

higher.

0

2000

CO

2

Maximum

Setpoint

CO2

MaxLv

AV:288

This is the CO

2

level at which

the Economizer

Min Damper
Position will

be reset to the

Economizer Max

Position in High

CO

2

. In between

the Min and

Max CO

2

levels

the Economizer

Min Damper

Position will be

proportionally

reset between the

confi gured Min

Damper Position

and the Max

Position in High

CO

2

.

0

2000

Bad CO

2

Sensor

CO2Alm

BI: 368

Failure of the

CO

2

Sensor.

Coil

Tempera-

ture

CoilTp

AI: 181

Current coil
temperature

reading.

Coil

Tempera-

ture Offset

ColTpOft

AV:284

If the Coil

Temperature

Sensor is reading

incorrectly, use

this offset to ad-

just the Sensor’s

Temperature.

-100

100

Bad Coil

Pressure

Sensor

ColPrAlm

BI: 367

Failure of the
Coil Pressure

Sensor. Will shut

unit down.

Coil Tem-

perature
Setpoint

CoilTpSt

AI: 334

This is the

current

calculated Coil

Suction

Temperature

target during

Dehumidifi cation

Mode.

NOTE:

When using Celsius scaling, all temperature values will

need to be divided by 10 by the BMS to properly read
the status and setpoint values, e.g., a value of 200º C
needs to be divided by 10 for an actual value of 20º C.

Advertising
This manual is related to the following products: