Parameter tables, 2 vcm-x modular bacnet parameters, Pt-link ii bacnet3 interface 44 – Orion System PT-Link II BACnet3 User Manual

Page 44: Zone

Advertising
background image

Zone

Zone

7. PARAMETER TABLES

PT-Link II BACnet3 Interface

44

7.2 VCM-X Modular BACnet Parameters

BACnet Properties for VCM-X Modular

Parameter

Name

Object

Description

Limits

Modulating

Compressor 2

MdCmp2

AI: 206

Current position
of the 2nd Stage

of Compressor

Modulation.

Head Pressure

Signal 1 on

Head Pressure

Module 1

HdPr1

AI: 207

Head Pressure

Signal 1 on Head

Pressure Module 1

Head Pressure

Signal 2 on

Head Pressure

Module 1

HdPr2

AI: 208

Head Pressure

Signal 2 on Head

Pressure Module 1

Condenser

Fan Signal 1

On Head Pres-

sure Module 1

CdFan1

AI: 209

Condenser Fan

Signal 1 On Head

Pressure Module 1

Condenser

Fan Signal 2

On Head Pres-

sure Module 1

CdFan2

AI: 210

Condenser Fan

Signal 2 On Head

Pressure Module 1

Title 24

Economizer

Feedback

T24EcFb

AI: 384

Current posi-

tion of feedback

from Economizer

actuator.

Title 24

Economizer

Alarms

AlmGrp5

AI: 391

Alarms for the 24

Title Economizer

Condenser

Fan Signal 1

On Head Pres-

sure Module 2

CdFan21

AI: 392

Condenser Fan

Signal 1 On Head

Pressure Module 2

Condenser

Fan Signal 2

On Head Pres-

sure Module 2

CdFan22

AI: 393

Condenser Fan

Signal 2 On Head

Pressure Module 2

Head Pressure

Signal 1 on

Head Pressure

Module 2

HdPr21

AI: 394

Head Pressure

Signal 1 on Head

Pressure Module 2

NOTE:

The following points for the VCM-X Modular, VCM-X

WSHP & RNE Controllers are additional points. All
points and property identifi ers in the VCM-X Control-
ler table (Section 7.5, page 48) also apply to the VCM-
X Modular, VCM-X WSHP, and RNE Controllers.

BACnet Properties for VCM-X Modular

Parameter

Name

Object

Description

Limits

Head Pressure

Signal 2 on

Head Pressure

Module 2

HdPr22

AI: 395

Head Pressure

Signal 2 on Head

Pressure Module 2

Remote VFD

Reset

RmVFDPos

AV: 258

Remote VFD

Position Reset

-1

100

Bad Return

Air Sensor

RaTpAlm

BI: 365

Alarm that indicates

a failure in the Re-

turn Air Sensor.

Title 24

Sensor Alarm

T24TpAlm

BI: 385

Outside Air or

Supply Air Tem-

perature Sensor is

shorted or missing.

Title 24 Not

Economiz-

ing When It

Should

T24NEWS

BI: 386

Economizer is

enabled but not fol-

lowing the desired

Economizer posi-

tion commanded.

Title 24

Economiz-

ing When It

Should Not

T24EWISN

BI: 387

Economizer is not

enabled but the

feedback signal

indicates a position
more open than the

minimum.

Title 24

Damper

Failure

T24DpAlm

BI: 388

Economizer is en-

abled but not with-

in 10% of desired

position within 150

seconds.

Title 24

Excess

Outdoor Air

T24ExsOA

BI: 389

Economizer

feedback is lost or
Economizer is not

following com-

manded position.

Advertising