Parameter tables, 6 sa controller bacnet parameters, Pt-link ii bacnet3 interface – Orion System PT-Link II BACnet3 User Manual

Page 55

Advertising
background image

PT-Link II BACnet3 Interface

7. PARAMETER TABLES

55

7.6 SA Controller BACnet Parameters

BACnet Properties for SA Controller

Parameter

Name

Object

Description

Limits

Condenser

Position 2

CdPos2

AI: 247

Current Condenser

Position for 2nd unit.

Dewpoint

Setpoint

DptSt

AV: 13

If the outdoor

dewpoint rises above

this setpoint, the

unit will activate the

Dehumidifi cation

Demand.

35

80

Occupied/

Mode

Enable

Cooling

Setpoint

OcpClSt

AV: 42

If the control

temperature rises one

degree above this

setpoint, the control

will activate the cool-

ing demand. If the

control temperature

is the Supply Air Sen-

sor, then the cooling

demand is always

active.

0

99

Occupied/

Mode

Enable

Heating

Setpoint

OcpHtSt

AV: 43

If the control

temperature drops

one degree below

this setpoint,

the control will

activate the heating

demand. If the

control temperature

is the Supply Air

Sensor, then there is

no heating demand.

99

Schedule

Force

SchdFrc

AV: 66

0 = Auto/

Unoccupied Mode

1 = Forced On

2 = Forced Off

0

2

Space

Sensor

Offset

SpcTpOst

AV: 71

If the Space

Temperature

Sensor is reading

incorrectly, you can

use this option to

enter an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

SAT

Cooling

Setpoint

SaClSt

AV: 77

Supply Air Setpoint

in Cooling Mode.

40

80

SAT

Heating

Setpoint

SaHtSt

AV: 78

Supply Air Setpoint

in Heating Mode.

40

200

BACnet Properties for SA Controller

Parameter

Name

Object

Description

Limits

Supply Air

Sensor Offset

SaTpOst

AV: 80

If the Supply Air

Temperature Sensor

is reading

incorrectly, you can

use this option to

enter an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

Warm Up

Setpoint

WmupSt

AV: 91

In a VAV

application, upon

entering the

occupied mode, the

Warm-up Demand

will be activated

if the return air

temperature falls

one degree below

this setpoint.

50

90

Coil

Temperature

Setpoint

CoilTpSt

AV: 107

This is the coil

suction temperature

target during

dehumidifi cation

mode. Produces

dewpoint in the

supply air

approximately 10°F

above this setpoint.

35

70

Indoor

Humidity

Setpoint

InRhSt

AV: 120

If the indoor

humidity rises

above this setpoint,

the unit will

activate the

Dehumidifi cation

Demand.

0

100

Unoccupied

Cooling

Offset

UnClOst

AV: 124

During the

Unoccupied Mode

of Operation, this

Setpoint spreads

the Occupied Cool-

ing Setpoint out by

a user adjustable

amount. If you do

not want Cooling to

operate during the

Unoccupied Mode,

use the default

setting of 30°F for

these setpoints.

0

30

Advertising