Parameter tables, 5 vcm-x bacnet parameters, Pt-link ii bacnet3 interface – Orion System PT-Link II BACnet3 User Manual

Page 51

Advertising
background image

PT-Link II BACnet3 Interface

7. PARAMETER TABLES

51

7.5 VCM-X BACnet Parameters

BACnet Properties for the VCM-X Controller

Parameter

Name

Object

Description

Limits

Bad Supply

Air Sensor

SaTpAlm

BI: 2

Alarm that

indicates a failure

in the

supply air sensor.

CO

2

Sensor

Installed

CO2Cfg

BI: 3

Status that

indicates the CO

2

function has been

confi gured.

Cooling

Enabled

ClEnbl

BI: 6

Status that indicates
mechanical cooling

is enabled.

Economizer

Enabled

EcoEnbl

BI: 15

Status that indicates

the economizer is

enabled.

Fan Start Up

Delay

FanDly

BI: 25

Status that indicates

the fan is

commanded to run,

but it is in the start

up delay mode.

Fan

Proving

Alarm

PofAlm

BI: 26

Alarm that

indicates a failure

in the fl ow of the

VFD blower.

Heating

Enabled

HtEnbl

BI: 30

Status that

indicates that

mechanical heating

is enabled.

High

Supply Air

Temperature

Alarm

HiSaAlm

BI: 33

The Supply Air
has risen above

the Hi SAT Cutoff

Setpoint. Heating

stages begin to deac-

tivate and the fan

continues to run.

Low Supply

Air

Temperature

Alarm

LoSaAlm

BI: 37

The Supply Air has

fallen below the Hi

SAT Cutoff Setpoint

and cooling stages

will begin to deacti-
vate. If the unit is in

Economizer, Vent,

or Heating Mode

the Supply Fan will

shut off.

MODGAS

II

Connected

MdHt2Ins

BI: 39

Status that indicates

the MODGAS II

controller is

connected.

Proof of

Flow

Confi gured

PofCfg

BI: 57

Status that indicates

the proof of fl ow

function has been

confi gured.

REHEAT II

Connected

Rt2Ins

BI: 58

Status that indicates

the MHGRV
controllers is

connected to the

system.

BACnet Properties for the VCM-X Controller

Parameter

Name

Object

Description

Limits

Mechanical

Cooling

Alarm

MchClAlm

BI: 94

Compressor Relays

are enabled but

the Supply Air

Temperature has

not fallen 5°F w/in

a user-adjustable

time period. This

does not indicate

compressors are

active and will not

shut the unit down.

Mechanical

Heating

Alarm

MchHtAlm

BI: 95

Heating Mode has

been initiated but

the Supply Air

Temperature has

not risen 5°F w/in

a user-adjustable

time period. This

does not indicate

heat stages are

active and will not

shut the unit down.

Dirty Filter

Detected

DrtFlAlm

BI: 96

Alarm that indicates

the fi lters are dirty.

Control

Temperature
Cool Failure

CtrlTpCF

BI: 108

This alarm is

activated if the

control temperature

does not get within

5°F to the occupied

cooling setpoint

in an hour in the

cooling mode. This

alarm is not used

in 100% outside air

units or supply air

control.

Control

Temperature

Heat Failure

CtrlTpHF

BI: 109

This alarm is

activated if the

control temperature

does not get within

5°F to the occupied

heating setpoint

in an hour in the

heating mode. This

alarm is not used

in 100% outside air

units or supply air

control.

Outdoor Air

Temperature

Lost

OaTpAlm

BI: 117

Alarm that

indicates a failure

in the outdoor air

temperature.

Smoke

Detected

Alarm

SmokeAlm

BI: 119

Alarm that indicates

the Smoke sensor

has been activated.

Space

Temperature

Sensor Lost

SpcTpAlm

BI: 101

Alarm that indicates

a failure in the

space temperature

sensor.