Parameter tables, 7 vcm bacnet parameters, Pt-link ii bacnet3 interface – Orion System PT-Link II BACnet3 User Manual

Page 63: 1 vcm pt-link ii bacnet, Property identifi er

Advertising
background image

PT-Link II BACnet3 Interface

7. PARAMETER TABLES

63

7.7 VCM BACnet Parameters

VcmExternal Relays1-2Bits::= BIT STRING {

ExpansionBoard1Relay1

(0),

ExpansionBoard1Relay2

(1),

ExpansionBoard1Relay3

(2),

ExpansionBoard1Relay4

(3),

ExpansionBoard2Relay1

(4),

ExpansionBoard2Relay2

(5),

ExpansionBoard2Relay3

(6),

ExpansionBoard2Relay4

(7)

}

VcmExternal Relays2-4Bits::= BIT STRING {

ExpansionBoard3Relay1

(0),

ExpansionBoard3Relay2

(1),

ExpansionBoard3Relay3

(2),

ExpansionBoard3Relay4

(3),

ExpansionBoard4Relay1 (4),
ExpansionBoard4Relay2

(5),

ExpansionBoard4Relay3

(6),

ExpansionBoard4Relay4

(7)

}

VcmAlarmStatusBits ::= BIT STRING {

Alarm

Group1

(0),

Alarm

Group2

(1),

Alarm

Group3

(2)

}

7.7.1 VCM PT-Link II BACnet

®

Property Identifi er:

The PT-Link II BACnet

®

Link amends the following property identity

to the BACnet

®

property identifi er.

BACNETPropertyIdentifi er :

WattBACNETScheduleForce ::= ENUMERATED {

NormalOperation

(0),

ForceOccupied

(1),

ForceUnoccupied

(2)

}

VcmUnitMode ::= ENUMERATED {

Unoccupied

(0),

RemoteContactOccupied (1),

NormalScheduleOccupied

(2),

PushButtonOrZoneOverride

(3),

HolidayModeActive

(4),

UnoccupiedZoneDemand

(5),

RemoteScheduleOverride (6),
CurrentOutputForceMode

(7),

SATHighOrLowCutOff

(8),

CO2OverrideInProgress

(9),

PurgeModeActive

(10)

}

VcmControlStatusBits ::= BIT STRING {

AhuControlEconomizer

(0),

NoOutdoorAirTempSensor

(1),

CarbonDioxideSensorPresent

(2),

HeatCoolStagingDisabled

(3),

Dehumidifi

cationMode

(4),

ModGasIIConnected

(5),

ReheatIIConnected

(6)

}

VcmOnBoardRelaysBits ::= BIT STRING {

OnBoardRelay1

(0),

OnBoardRelay2

(1),

OnBoardRelay3

(2),

OnBoardRelay4

(3),

OnBoardRelay5

(4)

}