7. PARAMETER TABLES

PT-Link II BACnet3 Interface

50

7.5 VCM-X BACnet Parameters

BACnet Properties for the VCM-X Controller

Parameter

Name

Object

Description

Limits

Warm Up

Setpoint

WmupSt

AV: 91

In a VAV

application, upon

entering the oc-

cupied mode, the

Warm-up Demand

will be activated

if the return air

temperature falls

one degree below

this setpoint.

50

90

Wet Bulb

Setpoint

WtblSt

AV: 92

The economizer is

enabled if the

outdoor tempera-

ture or wetbulb falls

below this setpoint.

0

80

Coil

Temperature

Setpoint

CoilTpSt

AV: 107

This is the coil

suction temperature

target during

dehumidifi cation

mode. Produces

dewpoint in the

supply air

approximately 10°F

above this setpoint.

35

70

Relief

Pressure
Setpoint

RfPrSt

AV: 118

This is the target

building pressure

to be maintained

by the VFD Relief

signal.

-0.2

0.2

Indoor

Humidity

Setpoint

InRhSt

AV: 120

If the indoor

humidity rises

above this setpoint,

the unit will acti-

vate the Dehumidi-

fi cation Demand.

0

100

Unoccupied

Cooling

Offset

UnClOst

AV: 124

During the

Unoccupied Mode

of Operation, this

Setpoint spreads the

Occupied Cooling

Setpoint out by

a user adjustable

amount. If you do

not want Cooling to

operate during the

Unoccupied Mode,

use the default

setting of 30°F for

these setpoints.

0

30

Unoccupied

Heating

Offset

UnHtOst

AV: 125

During the

Unoccupied Mode

of Operation, this

Setpoint spreads the

Occupied Heating

Setpoint out by

a user adjustable

amount. If you do

not want Heating to

operate during the

Unoccupied Mode,

use the default

setting of 30°F for

these setpoints.

0

30

BACnet Properties for the VCM-X Controller

Parameter

Name

Object

Description

Limits

CO

2

Setpoint

CO2St

AV: 149

When the CO

2

level rises above

the CO

2

Protection

Limit Max Level,

the Economizer’s

Minimum Position

will begin to reset

open proportionally

between the CO

2

Protection Limit

Max Level Setpoint

and the Reset

Range Setpoint.

0

3000

Minimum

Outside Air

Setpoint

MinEcoSt

AV: 151

This is the

minimum position

of the economizer

in the occupied

modes.

1

100

Static

Pressure
Setpoint

DuctPrSt

AV: 152

This is the target

duct pressure to be

maintained by the

VFD blower signal.

0.01

3

Preheater

Setpoint

PreHtSp

AV: 196

Low Outside Air

Ambient

Protection Setpoint

0

100

Outdoor

Air CFM

Setpoint

OACfmSt

AV: 203

Minimum desired

Outdoor Air CFM.

0.10

K

200 K

Outdoor Air

CFM Reset

Limit

OACfmRs

AV: 204

Maximum desired

Outdoor Air CFM
when CO

2

reaches

its reset limit.

0.10

K

200 K

Supply Air

Cool High

Reset

SaClRt

AV: 324

High Supply Air

Cooling Reset

Limit

40

150

Supply Air

Heat High

Reset

SaHtRt

AV: 325

High Supply Air

Heating Reset Limit

40

150

Cooling

Low Reset

Source

ClLoRt

AV: 326

Low Cool Reset

Source Setpoint

1

150

Cooling

High Reset

Source

ClHiRt

AV: 327

High Cool Reset

Source Setpoint

1

150

Heating

Low Reset

Source

HtLoRt

AV: 328

Low Heat Reset

Source Setpoint

1

150

Heating

High Reset

Source

HtHiRt

AV: 329

High Heat Reset

Source Setpoint

1

150