7. PARAMETER TABLES

37

7.1 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Indoor

Humidity

Setpoint

InRhSt

AV:289

If Coil Temp

Reset is being

used this is also

the lowest Space

RH value that

corresponds to

the Hi Coil Temp

Setpoint.

0

100

High

Indoor

Humidity

Reset
Limit

HiInRh

AV:292

During Coil

Temp Reset, this

is the highest

Space RH value

that corresponds

to the Low Coil

Temp Setpoint.

0

100

Indoor

Humidity

Setpoint

Mirror

InRhStM

AI: 114

Mirror of the
InRhSt “read

only.”

Leaving

Water

Tempera-

ture

LvWtrTp

AI:278

Leaving Water

Temperature

Value

Low

Ambient

Relay

Setpoint

LWAmbnt

AV:285

Temperature at
which the Low

Ambient Relay

will activate in

the Occupied

or Unoccupied

Mode.

-30

70

Mode

Select

Deadband

MdSelDb

AV: 339

This Setpoint

is added to and

subtracted from

the HVAC Mode

Setpoints to de-

termine when the

unit enters and

leaves a mode of

operation.

1

10

Modulat-

ing

Cooling
Position

MdClPos

AI: 115

Current position

of the modulat-

ing

cooling signal

(Chilled water or

digital

compressor).

Modulat-

ing Gas

Valve

Position

MdGs

VPos

AI:274

Current

position of
MODGAS

modulating gas

valve control.

Modulat-

ing

Heating

Position

MdHtPos

AI: 116

Current position

of the modulat-

ing

heating signal

(hot water or

SCR heat).

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Missing

MODGAS

Module

MisMDGAS

BI: 375

Alarm that

indicates that

the MODGAS

module is not

communicating

with the VCB-X

Controller.

Morning

Warm-Up

Return Air

Target

Setpoint

WmupTg

AV:281

If confi gured,

upon entering the

occupied mode,

the Warm-up

Demand will be

activated if the

return air tem-

perature is one

degree below

this setpoint.

50

90

Occupied

Cooling

Setpoint

OcpClSt

AV: 42

If the control

temperature rises

one degree above

this setpoint,

the control will

activate the

cooling demand.

If the control

temperature is

the Supply Air

Sensor, then the
cooling demand

is always active.

1

110

Occupied

Heating

Setpoint

OcpHtSt

AV: 43

If the control

temperature

drops one degree

below

this setpoint,

the control will

activate the

heating demand.

If the

control

temperature

is the Supply

Air Sensor, then

there is no

heating

demand.

1

110

Hood On

Outdoor

Air

Cooling

Setpoint

OaClSt

AV:45

This is the Cool-

ing Mode Enable

Setpoint used

only in Hood On

Mode.

1

110

Hood On

Outdoor

Air

Heating

Setpoint

OaHtSt

AV:46

This is the Heat-

ing Mode Enable

Setpoint used

only in Hood On

Mode.

1

110

Outdoor

Air CFM

OaCFM

AI: 193

Current Outdoor

Airfl ow

Measurement