Parameter tables, 6 sa controller bacnet parameters, Pt-link ii bacnet3 interface – Orion System PT-Link II BACnet3 User Manual

Page 57: 1 sa controller pt-link-bacnet, Property identifi er

Advertising
background image

PT-Link II BACnet3 Interface

7. PARAMETER TABLES

57

7.6 SA Controller BACnet Parameters

BACnet Properties for SA Controller

Parameter

Name

Object

Description

Drain Pan

Overfl ow

DrnAlm

BI: 244

Alarm that indicates overfl ow of

the drain pan.

Proof of

Water Flow

Alarm

PoWFAlm

BI: 245

Alarm that indicates no

Proof of Water Flow.

Entering Air

Temperature

Alarm

EaTpAlm

BI: 248

Alarm that indicates

failure in the Entering Air

Temperature Sensor.

BACnet Properties for SA Controller

Parameter

Name

Object

Description

Control

Temperature

Heat Failure

CtrlTpHF

BI: 109

This alarm is activated if the
control temperature does not

get within 5°F to the occupied

heating setpoint in an hour in the

heating mode. This alarm is not

used in 100% outside air units or

supply air control.

Space

Temperature

Sensor Lost

SpcTpAlm

BI: 101

Alarm that indicates a failure in

the space temperature sensor.

On Board

Relay 1

OnRly1

BI: 127

Current status of relay 1.

On Board

Relay 2

OnRly2

BI: 128

Current status of relay 2.

On Board

Relay 3

OnRly3

BI: 129

Current status of relay 3.

On Board

Relay 4

OnRly4

BI: 130

Current status of relay 4.

On Board

Relay 5

OnRly5

BI: 131

Current status of relay 5.

Expansion

Relay 1

ExRly1

BI: 133

Current status of relay 6.

Expansion

Relay 2

ExRly2

BI: 134

Current status of relay 7.

Expansion

Relay 3

ExRly3

BI: 135

Current status of relay 8.

Expansion

Relay 4

ExRly4

BI: 136

Current status of relay 9.

Expansion

Relay 5

ExRly5

BI: 137

Current status of relay 10.

Expansion

Relay 6

ExRly6

BI: 138

Current status of relay 11.

Expansion

Relay 7

ExRly7

BI: 139

Current status of relay 12.

Expansion

Relay 8

ExRly8

BI: 140

Current status of relay 13.

Expansion

Relay 9

ExRly9

BI: 141

Current status of relay 14.

Expansion

Relay 10

ExRly10

BI: 142

Current status of relay 15.

Expansion

Relay 11

ExRly11

BI: 143

Current status of relay 16.

Expansion

Relay 12

ExRly12

BI: 144

Current status of relay 17.

Expansion

Relay 13

ExRly13

BI: 145

Current status of relay 18.

Expansion

Relay 14

ExRly14

BI: 146

Current status of relay 19.

Expansion

Relay 15

ExRly15

BI: 147

Current status of relay 20.

Expansion

Relay 16

ExRly16

BI: 148

Current status of relay 21.

Emergency

Shutdown

Alarm

EmerAlm

BI: 219

Alarm that indicates

Emergency Shutdown.

7.6.1 SA Controller PT-Link-BACnet

®

Property Identifi er:

The PT-Link-BACnet

®

Link amends the following property identity to

the BACnet

®

property identifi er.

BACNETPropertyIdentifi er :

SAUnitMode ::= ENUMERATED {

Unoccupied

(0),

RemoteContactOccupied (1),
NormalScheduleOccupied

(2),

PushButtonOrZoneOverride

(3),

HolidayModeActive

(4),

UnoccupiedZoneDemand

(5),

RemoteScheduleOverride (6),
CurrentOutputForceMode

(7),

SATHighOrLowCutOff

(8),

CO2OverrideInProgress

(9),

PurgeModeActive

(10)

}

SAControlStatusBits ::= ENUMERATED {

Off

(0),

Vent

(1),

Cool

(2),

Heat

(3),

Dehum

(4),

Dehum

Cool

(5),

Dehum

Heat

(6),

Warm

Up

Mode

(7)

}