PT-Link II BACnet3 Interface

7. PARAMETER TABLES

47

7.4 VCM-X WSHP (Coil) BACnet Parameters

BACnet Properties for VCM-X WSHP (Coil)

Parameter

Name

Object

Description

Limits

Proof of Water

Flow Alarm

POWF1Alm

BI: 232

Alarm that

indicates no

Proof of Water

Flow.

Module

Communica-

tions

Alarm

ComMAlm

BI: 234

Alarm that

indicates that

one or more

Modules are

not commu-

nicating with

the VCM-X

WSHP

Controller.

Bad Return Air

Sensor

RaTpAlm

BI: 365

Alarm that

indicates

a failure in

the Return Air

Sensor.

Title 24 Econo-

mizer Feedback

T24EcFb

AI: 384

Current

position of

feedback from

Economizer

actuator.

Title 24

Sensor Alarm

T24TpAlm

BI: 385

Outside Air

or Supply Air

Temperature

Sensor is

shorted or

missing.

Title 24 Not

Economizing

When It Should

T24NEWS

BI: 386

Economizer

is enabled but

not following

the desired

Economizer

position com-

manded.

Title 24 Econo-
mizing When It

Should Not

T24EWISN

BI: 387

Economizer

is not enabled

but the feed-

back signal

indicates a

position more

open than the

minimum.

Title 24 Damper

Failure

T24DpAlm

BI: 388

Economizer

is enabled but

not within

10% of de-

sired position

within 150

seconds.

Title 24 Excess

Outdoor Air

T24ExsOA

BI: 389

Economizer

feedback

is lost or

Economizer is

not following

commanded

position.

BACnet Properties for VCM-X WSHP (Coil)

Parameter

Name

Object

Description

Limits

Modulating

Compressor 2

MdCmp2

AI: 206

Current

position of the

2nd Stage of

Compressor

Modulation.

Head Pressure 1

HdPr1

AI: 207

Head Pressure

for
1st

Compressor

Head Pressure 2

HdPr2

AI: 208

Head Pressure

for

2nd

Compressor

Condenser

Fan 1

CdFan1

AI: 209

Condenser

Fan 1

Signal Status

Condenser

Fan 2

CdFan2

AI: 210

Condenser

Fan 2

Signal Status

Water Temp. A

WaterTpA

AI: 220

Current water

temperature.

Remote VFD

Reset

RmVFDPos

AV:
258

Remote VFD

Position Reset

-1

100

Compressor A

Low Suction

Pressure Alarm

A1LSPAlm

BI: 222

Alarm that

indicates

Suction

Pressure for

Circuit A is

below the

Low Suction

Pressure Cool-

ing (Heating)

Setpoint.

Compressor A

Lockout Alarm

A1LktAlm

BI: 223

Alarm that in-

dicates Circuit

A Compres-

sors are locked

out.

Compressor B

Low Suction

Pressure Alarm

B1LSPAlm

BI: 226

Alarm that

indicates

Suction

Pressure for

Circuit B is

below the

Low Suction

Pressure Cool-

ing (Heating)

Setpoint.

Compressor B

Lockout Alarm

B1LktAlm

BI: 227

Alarm that in-

dicates Circuit

B Compres-

sors are locked

out.

Low Water

Temperature

Alarm

LWT1Alm

BI: 230

Alarm that

indicates water

temperature
is below the

Leaving Water

Safety Set-

point (Heating

only).