1. GENERAL INFORMATION

PT-Link II BACnet3 Interface

4

The OE368-23B-BACNET3, PT-Link II BACnet

®

provides bi-direction-

al communication between your BACnet

®

MS/TP protocol network and

up to four* of any of the following types of Orion controllers—VCM-X,
VCB-X, RNE, SA, VCM, MUA II, or VAV/CAV:

VCM-X Controller (SS1026, SS1030, SS1032, SS1033,
SS1034, Y200920)

VCB-X Controller (SS1051)

RNE Controller (SS1045)

SA Controller (Y200921)

VCM Controller (SS1016, Y200409, Y200616, Y200822)

**VAV/CAV Controller (SS1003, Y200301) and
MUA II Controller (SS1004, Y200405)

To determine what controller you have, you must look at the label located
on the controller. NOTE: The label is located on the EPROM on older
devices. If the controller label does not match any of the SS or Y numbers
listed above, your controller will not work with the PT-Link II BACnet

®

.

*NOTE: The PT-Link II BACnet

®

device can be used to con-

nect to four Orion controllers. If more than four Orion
controllers are present in a system, you will need ad-
ditional PT-Link II BACnet

®

devices.

**

NOTE: Documentation is available for MUA II/VAV/CAV on

our Orion Controls website: www.orioncontrols.com.

1.1.1 Data Sharing

Provides values from points on the Orion side of the

gateway to BACnet

®

devices as if the values were

originating from BACnet

®

objects.

Allows BACnet

®

devices to modify point values on the

Orion controller side of the PT-Link II BACnet

®

by using

standard

BACnet

®

write services.

1.1.2 Scheduling

Allows BACnet

®

devices to send Schedule events

to the Orion controller side of the gateway by using

standard

BACnet

®

services.

1.1.3 Hardware Specifi cations

Technical Data

BACnet®-MS/TP Loop

9600, 19200, 38400, 76800 Mbps

Controller Loop

RS-485, 9600 Baud Rate

Network Protocol

BACnet®

Protocol
(WattMaster Loop)

HSI Open Protocol Token Passing

Power Input Voltage

24 VAC

Power Consumption

10 VA Maximum

Operating Temp

-30°F to 150°F

Operating Humidity

90% RH Non-Condensing

Weight

4.5 oz.

Table 1: PT-Link II BACnet

®

Interface

Technical Data

1.1.4 System Requirements

The

PT-Link II BACnet

®

interface is packaged and

assembled for panel mounting. Panel mounting components

are included for your convenience.

Computer running Microsoft Windows

TM

operating

system.

Ethernet Crossover Cable (supplied).

PT-Link II BACnet software—located on included CD-

ROM and downloadable from www.orioncontrols.com.