7. PARAMETER TABLES

PT-Link II BACnet3 Interface

56

7.6 SA Controller BACnet Parameters

BACnet Properties for SA Controller

Parameter

Name

Object

Description

Limits

Unoccupied

Heating

Offset

UnHtOst

AV: 125

During the

Unoccupied Mode

of Operation, this

Setpoint spreads

the Occupied

Heating Setpoint

out by a user

adjustable amount.

If you do not want
Heating to operate

during the Unoc-

cupied Mode, use

the default setting

of 30°F for these

setpoints.

0

30

Static

Pressure
Setpoint

DuctPrSt

AV: 152

This is the target

duct pressure to be

maintained by the

VFD blower signal.

0.01

3

Preheater

Setpoint

PreHtSp

AV: 196

Low Outside Air

Ambient

Protection Setpoint

0

100

Entering

Air Offset

Setpoint

EaTpOst

AV: 238

If the Entering

Air Temperature

Sensor is reading

incorrectly, you

can use this option

to enter an offset

temperature to

adjust the Sensor’s

Temperature.

Entering

Water

Offset

Setpoint

EwTpOst

AV: 239

If the Entering

Water Temperature

Sensor is reading

incorrectly, you

can use this option

to enter an offset

temperature to

adjust the

Sensor’s

Temperature.

Supply Air

Cool High

Reset

SaClRt

AV: 324

High Supply Air

Cooling Reset

Limit

40

150

Supply Air

Heat High

Reset

SaHtRt

AV: 325

High Supply Air

Heating Reset

Limit

40

150

Cooling Low
Reset Source

ClLoRt

AV: 326

Low Cool Reset

Source Setpoint

1

150

Cooling High

Reset Source

ClHiRt

AV: 327

High Cool Reset

Source Setpoint

1

150

Heating Low
Reset Source

HtLoRt

AV: 328

Low Heat Reset

Source Setpoint

1

150

Heating High

Reset Source

HtHiRt

AV: 329

High Heat Reset

Source Setpoint

1

150

Fan Start Up

Delay

FanDly

BI: 25

Status that indicates

the fan is com-

manded to run, but

it is in the start up

delay mode.

BACnet Properties for SA Controller

Parameter

Name

Object

Description

Bad Supply

Air Sensor

SaTpAlm

BI: 2

Alarm that indicates a failure in

the supply air sensor.

Cooling

Enabled

ClEnbl

BI: 6

Status that indicates

mechanical cooling is enabled.

Economizer

Enabled

EcoEnbl

BI: 15

Status that indicates

the economizer is enabled.

Fan

Proving

Alarm

PofAlm

BI: 26

Alarm that indicates a failure in

the fl ow of the VFD blower.

Heating

Enabled

HtEnbl

BI: 30

Status that indicates that me-

chanical heating is enabled.

High

Supply Air

Temperature

Alarm

HiSaAlm

BI: 33

The Supply Air has risen above

the Hi SAT Cutoff Setpoint.

Heating stages begin to

deactivate and the fan continues

to run.

Low Supply

Air

Temperature

Alarm

LoSaAlm

BI: 37

The Supply Air has fallen below

the Hi SAT Cutoff Setpoint and

cooling stages will begin to

deactivate. If the unit is in

Economizer, Vent, or Heating

Mode the Supply Fan

will shut off.

MODGAS II

Connected

MdHt2Ins

BI: 39

Status that indicates

the MODGAS II controller is

connected.

REHEAT II

Connected

Rt2Ins

BI: 58

Status that indicates

the MHGRV

controllers is connected to the

system.

Mechanical

Cooling

Alarm

MchClAlm

BI: 94

Compressor Relays are enabled
but the Supply Air Temperature

has not fallen 5°F w/in a user-

adjustable time period. This does

not indicate compressors are

active and will not

shut the unit down.

Mechanical

Heating

Alarm

MchHtAlm

BI: 95

Heating Mode has been initiated

but the Supply Air Temperature

has not risen 5°F w/in a

user-adjustable time period.

This does not indicate heat

stages are active and will not

shut the unit down.

Dirty Filter

Detected

DrtFlAlm

BI: 96

Alarm that indicates the fi lters

are dirty.

Control

Temperature
Cool Failure

CtrlTpCF

BI: 108

This alarm is activated if the
control temperature does not

get within 5°F to the occupied

cooling setpoint in an hour in the

cooling mode. This alarm is not

used in 100% outside air units or

supply air control.