Parameter tables, 5 vcm-x bacnet parameters, Pt-link ii bacnet3 interface – Orion System PT-Link II BACnet3 User Manual

Page 49

Advertising
background image

PT-Link II BACnet3 Interface

7. PARAMETER TABLES

49

7.5 VCM-X BACnet Parameters

BACnet Properties for the VCM-X Controller

Parameter

Name

Object

Description

Limits

Modulating

Cool

Position

MdClPos

AI: 115

Current position of

the modulating

cooling signal

(Chilled water or

digital compressor).

Modulating

Heat

Position

MdHtPos

AI: 116

Current position of

the modulating

heating signal (hot

water or SCR heat).

Unit Mode

UnitMode

AI: 123

See page 53.

Return Air
CO

2

Level

CO2Level

AI: 150

Current value of the

CO

2

sensor.

Bypass

Damper
Position

ByPas-

Dmp

AI: 153

Current position of

the bypass damper

signal.

Return

Damper
Position

RaDmp

AI: 154

Current position of

the return damper

signal.

Coil

Temperature

CoilTp

AI: 181

Current coil

temperature reading

added on version

1.09.

Outdoor Air

CFM

OaCFM

AI: 193

Current Outdoor

Airfl ow

Measurement

Exhaust

CFM

EtCFM

AI: 194

Current Exhaust

Airfl ow

Measurement

Supply Air

CFM

SaCFM

AI: 195

Current Supply

Airfl ow

Measurement

Current

Calculated

OA CFM

setpoint

OACfm-

StM

AI: 205

Current calculated

Outdoor Air CFM

based on CO

2

level.

Dewpoint

Setpoint

DptSt

AV: 13

If the outdoor

dewpoint rises

above this setpoint,

the unit will

activate the

Dehumidifi cation

Demand.

35

80

Occupied/

Mode

Enable

Cooling

Setpoint

OcpClSt

AV: 42

If the control tem-

perature rises one
degree above this

setpoint, the control

will activate the

cooling demand. If

the control tempera-

ture is the Supply

Air Sensor, then the

cooling demand is

always active.

0

99

BACnet Properties for the VCM-X Controller

Parameter

Name

Object

Description

Limits

Occupied/

Mode

Enable

Heating

Setpoint

OcpHtSt

AV: 43

If the control

temperature drops

one degree below

this setpoint,

the control will

activate the heating

demand. If the

control

temperature

is the Supply Air

Sensor, then there is

no heating demand.

0

99

Outdoor

Air Sensor

Offset

OaTpOst

AV: 53

If the Outdoor

Temperature Sensor

is reading

incorrectly, you can

use this option to

enter an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

Return

Air Sensor

Offset

RaTpOst

AV: 65

If the Return Tem-

perature Sensor is

reading incorrectly,

you can use this

option to enter an

offset temperature

to adjust the Sen-

sor’s Temperature.

-100

100

Schedule

Force

SchdFrc

AV: 66

0 = Auto/

Unoccupied Mode

1 = Forced On

2 = Forced Off

0

2

Space

Sensor

Offset

SpcTpOst

AV: 71

If the Space

Temperature

Sensor is reading

incorrectly, you can

use this option to

enter an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

SAT

Cooling

Setpoint

SaClSt

AV: 77

Supply Air Setpoint

in Cooling Mode.

40

80

SAT

Heating

Setpoint

SaHtSt

AV: 78

Supply Air Setpoint

in Heating Mode.

40

200

Supply

Air Sensor

Offset

SaTpOst

AV: 80

If the Supply Air

Temperature Sensor

is reading incor-

rectly, you can use

this option to enter

an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

Advertising
This manual is related to the following products: