PT-Link II BACnet3 Interface

7. PARAMETER TABLES

35

7.1 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Digital

Compres-

sor Cutoff

DigCmpCf

BI: 379

Occurs if the

digital compres-

sor discharge

temperature rises

above 268°F
or the sensor

is shorted. The

compressor is

disabled.

Digital

Com-

pressor

Lockout

DigCmpLk

BI: 380

Occurs if fi ve

Digital Compres-

sor Cutoffs

occur within

four hours. The

compressor will

be locked out.

Dirty Filter

Alarm

DrtFlAlm

BI: 96

Alarm that

indicates the

fi lters are dirty.

Economiz-

er Enabled

EcoEnbl

AI: 15

Status that

indicates the

economizer is

enabled.

Economiz-

er Enable

Setpoint

EcoEnbSt

AV:283

The economizer

is enabled if the

outdoor drybulb,

dewpoint, or

wetbulb temper-

ature falls below

this setpoint.

-30

80

Economiz-

er Position

EcoPos

AI: 16

Current position

of the econo-

mizer damper.

Max

Economiz-

er in Heat

Mode

MaxEcoHt

AV: 353

Max position

the Economizer

Damper can

open in the Heat-

ing Mode. Takes

priority over

Max Position in

High CO

2

.

0%

100%

Max

Econo-

mizer in

High CO2

Mode

MaxEcoCO

AV: 354

The maximum

value the

Economizer

Minimum Posi-

tion can be reset

up to during CO

2

override.

0%

100%

Minimum

Econo-

mizer

Position

MinEcoSt

AV: 151

Minimum

position of the

economizer in

the occupied

mode.

0

100

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Force

Econo-

mizer

FrcEcono

AV: 267

Overrides all

other Outdoor

Air Damper

position com-

mands so as to

maintain this

fi xed position.

Confi guring

for “Auto” will

restore normal

unit control of

the Outdoor Air
Damper/Econo-

mizer operation.

0%

100%

Auto=65535

Emergency

Heat

Enabled

EmHtEnbl

BI: 364

Shows the Emer-

gency Heat is

enabled based on

the Compressor

Heating Lockout.

Exhaust

Fan CFM

EtCFM

AI:194

Current Exhaust

Airfl ow

Measurement

Missing
Exhaust

CFM

Sensor

ExtCfmSr

BI: 371

Indicates that the

Exhaust CFM

Sensor is not

detected.

Exhaust

Fan Speed

EtFnSpd

AI: 273

Current value of

the VFD relief

fan signal.

Missing

EM1

Expansion

Module

MisEM1

BI: 366

Indicates that the

EM1 Expansion

Module is not

communicating

with the VCB-X

Controller.

Fan

Starting

Delay

FanDly

AI: 25

Indicates the

current fan status
related to request

to run, fan start-

ing delay or POF

failure.

0=No Request

1=Fan

Running

2=Fan Start

Delay

3=POF Failure

Leaving

H2O

Offset

LvH2OOst

AV: 347

If the Leaving

Water Tempera-

ture Sensor is

reading incor-

rectly, use this to
enter an offset to

adjust the Sen-
sor’s Tempera-

ture.

-100

100

Water

Proof

of Flow

Failure

H2OProf

BI: 382

Indicates no

Proof of Water

Flow.