Parameter tables, 1 vcb-x bacnet parameters, Pt-link ii bacnet3 interface – Orion System PT-Link II BACnet3 User Manual

Page 33

Advertising
background image

PT-Link II BACnet3 Interface

7. PARAMETER TABLES

33

7.1 VCB-X BACnet Parameters

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Low Coil

Tem-

perature
Setpoint

Limit

LoClTpSt

AV:295

This is the low-
est that the Coil

Temperature will

be reset to during

Space Humid-

ity Reset of the

Coil Suction
Temperature

Setpoint. If no

coil temperature

reset is required,

this value should

be set the same

as the High Coil

Temperature

Setpoint.

35

70

High Coil

Tem-

perature
Setpoint

Limit

HiClTpSt

AV:296

This is the high-

est that the Coil

Temperature will

be reset to during

Space Humid-

ity Reset of the

Coil Suction
Temperature

Setpoint. If no

coil temperature

reset is required,

this value should

be set the same

as the Low Coil

Temperature

Setpoint.

35

70

Com-

pressor

Discharge

Tempera-

ture

DschgTp

AI: 331

Current value of

the Compressor
Discharge Tem-

perature Sensor.

Bad Com-

pressor

Discharge

Sensor

DschgAlm

BI: 369

Failure of the

Digital Compres-

sor Discharge

Temperature

Sensor.

Control

Mode

CtrlMod

AI: 97

1=Constant

Volume

2=Supply Air
Cooling Only

3=Outdoor

Temp Control

4=Single Zone

VAV

5=Supply Air

Tempering

6=Space Temp

Control w/

High OA

Content

Unoccupied

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Control

Tem-

perature
Cooling

Failure

CtrlTpCF

BI: 108

Activated if the

control tempera-
ture does not get

within 5°F to the

occupied cooling

setpoint in an

hour in the cool-

ing mode. This

alarm is not used

in 100% outside

air units or sup-

ply air control.

Control

Tem-

perature

Heating

Failure

CtrlTpHF

BI: 109

Activated if the

control tempera-
ture does not get

within 5°F to the
occupied heating

setpoint in an

hour in the heat-

ing mode. This

alarm is not used

in 100% outside

air units or sup-

ply air control.

High

Control

Mode

Tempera-

ture

HiCtrlMd

BI: 377

Occurs when the

Controlling Sen-

sor Temperature

rises above the

Cooling Mode

Enable Setpoint

plus the Control

Mode High

Alarm Offset.

Applies only to

Space or Return

Air Temperature

controlled units.

Low Con-

trol Mode

Tempera-

ture

LoCtrlMd

BI: 378

Occurs when the

Controlling Sen-

sor Temperature

falls below the

Heating Mode

Enable Setpoint

minus the Con-

trol Mode Low

Alarm Offset.

Applies only to

Space or Return

Air Temperature

controlled units.

Cooling

Low Reset

Source

ClLoRt

AV: 326

If doing Supply

Air Setpoint

Reset, this is

the Low Reset

Source value in

Cooling that will

correspond to

the Supply Air

Cool High Reset

Setpoint.

1

150