Westermo MRD-3x0 User Manual

Page 182

Advertising
background image

182

6623-3201

Connection timeout
When this field is set to a value greater than 0, the serial serv-
er will close connections that have had no network receive 
activity for longer than the specified period

Transmission mode
Select RTU or ASCII, based on the Modbus slave equipment 
attached to the port.

Response timeout
This is the timeout (in milliseconds) to wait for a response 
from a serial slave device before retrying the request or 
returning an error to the Modbus master.

RTU framing timeout
This is the timeout (in milliseconds) the the serial server will 
use to determine the boundaries of Modbus/RTU packets 
received on the serial port.

Retries
Should no valid response be recieved from a Modbus slave, 
the value in this field determines the number of times the 
serial server will retransmit requests before giving up.

For information on setting the Port Configuration, see section 
7.2.1.