Programming 5 - 23

Digital Operator and Control Panel Display for PI Control

In Table 5.3, the o1-0X parameter listed setup the Drive display to indicate 3 variables for PI control as in Figure 5.14 when

the HAND/OFF/AUTO switch is in AUTO.

Fig 5.14 Drive Display for PI Control, AUTO Mode

Table 5.3 PI Control Parameter Settings in Bypass Units

PARAMETER

NUMBER

SETTING

UNITS

DESCRIPTION

KEYPAD DISPLAY

For Bypass Setting

Bypass & PI

Control

Bypass

Default

b1-01

SEE TABLE

5.4

SEE TABLE

5.2

N/A

Frequency Reference Selection – Selects the
speed command input source

Reference Source / Terminals

b5-01

1

0

N/A

PI Mode Selection – Enables PI mode

PI Mode Setting / PI Mode

H1-03

SEE TABLE

5.4

SEE TABLE

5.2

N/A

Terminal S5 Function Selection – Set for PI
Disable, turn off PI controller

Terminal S5 Sel / PI Disable

H1-04

SEE TABLE

5.4

4

N/A

Terminal S6 Function Selection – Set for
various operating modes

Terminal S6 Sel / Com/Inv Sel 2,
for example

H3-02

100

SEE TABLE

5.2

%

Terminal A1 Gain Setting

Terminal / (0-1000)

H3-08

SEE TABLE

5.4

SEE TABLE

5.2

N/A

Terminal A2 Signal Level – Signal selection,
0 to 10 VDC (Drive control board switch

S1-2 off) or 4 to 20 mA (Drive control board
switch S1-2 on)

Term A2 Signal / 0-10 VDC

H3-09

B

SEE TABLE

5.2

N/A

Terminal A2 Function Selection – Selects
how this input will be used by the Drive

Terminal A2 Sel / PI Feedback

o1-03

1

0

%

Digital Operator Display Selection – Set for
percent

Display Scaling / (0-39999)

o1-06

1

0

N/A

User Monitor Selection Mode – Enables a
custom display for PI Control monitoring

Monitor Mode Sel / 1: 3 Non
Selectable

o1-08

24

3

N/A

Third Line User Monitor Selection – Display
PI Feedback

3rd Monitor Sel / 24: PI Feed-
back

PI SETPOINT

FWD

REV

SEQ

REF ALARM

AUTO

- - - - - - - - - - - - - - - - - - - - - - - - - - - - -

OUTPUT

PI FEEDBACK

RUN

Monitor

DATA

ESC

MENU

ENTER

RESET

STOP