Preventive maintenance, Table 7.3 preventive maintenance, Maintenance 7 - 3 – Yaskawa E7B Drive Bypass User Manual

Page 211

Advertising
background image

Maintenance 7 - 3

Preventive Maintenance

If the Drive is used under the following conditions, it may be necessary to inspect more often:
• High ambient temperatures, humidity or altitudes above 3,300 feet
• Frequent starting and stopping
• Fluctuations of the AC power supply or load
• Excessive vibration and/or shock loading
• Poor environment, including dust, metal particles, salt, sulfuric acid, and chlorine

Table 7.3 Preventive Maintenance

Inspection Points

Item

Check Points

Every 3-6 Months

Yearly

General

Environment

Ambient Temperature

Humidity

Dust

Harmful Gas

Oil Mist

X

X

X

X

X

Equipment

Abnormal vibration or noise

X

AC Power Supply

Main circuit & control voltage

X

AC Power Circuit &

Devices

Conductors & Wire

Connections

Loose lugs, screws & wires

Hot spots on parts

Corrosion

Bent conductors

Breakage, cracking or discoloration

Check spacing

X
X
X
X
X
X

Transformers & Reactors

Discoloration or Noise

X

Terminal Blocks

Loose, damaged

X

DC Bus Capacitors

Leakage

Ruptures, broken, expansion

Capacitance & insulation resistance

X
X
X

Relays & Contactors

Noisy

Contact discoloration

X
X

Soft Charge Resistors

Cracked

Discoloration

X
X

Control Circuits

Operation

Speed reference voltage/current

I/O contact operation

Relay logic

X
X

Cooling System

Cooling Fans/Fins & Heatsink

Abnormal fan noise

Loose connectors

Free of accumulation

X

X

X

Keypad/Front Panel

Display

Digital Operator and

Front Panel

LEDs

Monitor display values

Key and selector switch functionality

Clean

X
X

X
X

Advertising