Bypass run indicator, Table 3.8 bypass run indicator, Motor ol/safeties fault indicator – Yaskawa E7B Drive Bypass User Manual

Page 70: Table 3.9 motor ol/safeties fault indicator, Control panel 3 - 6

Advertising
background image

Control Panel 3 - 6

Bypass Run Indicator

Motor OL/Safeties Fault Indicator

Table 3.8 Bypass Run Indicator

Indicator Status

Description

On

The Bypass has been given a run command in the HAND or AUTO
mode.

Or, the operation has been remotely transferred to Bypass using the
switch selectable “Remote Transfer to Bypass” feature (S104) via a
BAS contact closure at terminals TB1-25 and TB1-26.

Or, the operation has been automatically transferred to Bypass after a
Drive fault condition via the switch selectable “Auto Transfer to
Bypass” feature (S103).

Or, the operation has been transferred to Bypass using the switch-select-
able “Smoke Purge” feature (S105) via a contact closure at terminals
TB1-17 and TB1-18.

The motor is running at full speed across-the-line and the Drive is de-
energized.

Off

The Bypass has no run command in either the HAND or AUTO modes.
The unit may be operating in Drive mode.

Table 3.9 Motor OL/Safeties Fault Indicator

Indicator Status

Description

On

The motor overload (S10) has tripped OFF de-energizing both the
Drive and Bypass Circuits.

Or, the NC “motor safety circuit” connected to terminals TB1-1 and
TB1-2 has an open circuit condition.

Off

The motor overload (S10) and NC “motor safety circuit” are satisfied.

Advertising