Diagnostic & Troubleshooting 6 - 9

PF

Input Pha Loss

Input Phase Loss
Drive input power supply has an open phase
or has a large imbalance of input voltage.

Open phase on the input of the
Drive.

Check the input voltage.

Loose terminal screws at
R/L1, S/L2 or T/L3.

Tighten the terminal screws.

Momentary power loss
occurred.

Check the input voltage.

Input voltage fluctuation too
large.

Check the input voltage.

Parameter L8-06 value is set
incorrectly.

Verify parameter L8-06 is set

correctly per the kVA tables on
pages B-4 and B-5. Adjust L8-06
according to your application.
The higher the value the less

sensitive it becomes.

CAUTION:

Changing this

parameter from the factory

default setting may cause
Drive failure and void the

product warranty. (Consult

the factory for application
assistance).

PUF

DC Bus Fuse Open

DC Bus Fuse
Detects if the DC bus fuse has opened

Shorted output transistor(s) or
terminals.

Remove power from the Drive.

Disconnect the motor.

Perform the checks without
power in Table 6.6.

Replace the shorted

component(s).

Replace the defective fuse.

RH

DynBrk Resistor

Dynamic Braking Resistor
The protection of the dynamic braking
resistor based on setting of L8-01

Overhauling load, extended
dynamic braking duty cycle,
defective dynamic braking
resistor.

Verify dynamic braking duty
cycle.

Monitor DC bus voltage.

Replace dynamic braking
resistor.

RR

DynBrk Transistr

Dynamic Braking Transistor
The dynamic braking transistor failed.

Shorted dynamic braking
transistor, high DC bus
voltage, defective dynamic
braking resistor.

Cycle power off and on to the
Drive.

Replace defective dynamic
braking transistor or resistor.

..

Monitor DC bus voltage.

Table 6.1 Fault Displays and Processing

Digital

Operator Display

Description

Cause

Corrective Action