Electrical Installation 2 - 9

Annunciation Contacts

Contacts for customer use are provided and wired to TB1 as follows for use as annunciators of Bypass unit operation. All
are 1 amp at 120 VAC contacts.

The “Motor OL/Safeties Fault” and “Drive Fault” annunciation contacts sequence of operation is shown below:

Table 2.4 Annunciation Contacts

Function

Type

TB1 Terminals

Motor OL/Safeties Fault

Form C

14-15-16

Bypass Run

Form A

9-10

Drive Run

Form A

7-8

Drive Fault

Form C

11-12-13

Drive Fault

Motor OL/Customer

Safeties Fault

13

16

15

14

16

15

14

16

15

14

13

12

11

13

12

11

12

11

Power Off

Power on; no drive fault
and no MOL/CS fault

Power on; drive fault
and MOL/CS fault