Parameters A - 12

Digital Inputs

H1-01

Terminal S3 Function
Selection
Terminal S3 Sel

0: 3-wire control
FWD/REV selection for 3-wire sequence
1: Local/Remote Sel
Hand/Auto Selection - Closed = Hand, Open = Auto
2: Option/Inv Sel
Selects source of speed command and sequence
Closed = b1-01 & b1-02, Open = Option Card
3: Multi-Step Ref 1
Closed = speed command from d1-02 or Aux Terminal
Open = speed command determined by b1-01
4: Multi-Step Ref 2
Closed = speed command from d1-03 or d1-04
Open speed command determined by b1-01
6: Jog Freq Ref

Closed = speed command from d1-17
Open = speed command determined by b1-01
7: Multi-Acc/Dec 1
Closed = Accel & Decel Ramps determined by C1-03 & C1-04
Open = Accel & Decel Ramps determined by C1-01 & C1-02
8: Ext BaseBlk N.O.

Closed = Output transistors forced off, Open = Normal operation
9: Ext BaseBlk N.C.

Closed = Normal Operation, Open = Output transistors forced

off
A: Acc/Dec RampHold
Closed = Acceleration suspended and speed held, Open =

Normal Operation

C: Term A2 Enable
Closed = Terminal A2 is active, Open = Terminal A2 is disabled
F: Term Not Used
Terminal has no effect
10: MOP Increase
Closed = Speed Command Increases, Open = Speed Command

Held.

Must be set in conjunction with MOP Decrease and b1-02 must

be set to 1.

11: MOP Decrease

Closed = Speed Command Decreases, Open = Speed Command

Held.

Must be set in conjunction with MOP Increase and b1-02 must

be set to 1.

(Continued on next page)

0 to 6E

24

Programming

H1-02

Terminal S4 Function
Selection
Terminal S4 Sel

0 to 6E

14

Programming

Table A.1 Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu