Enclosure data, Table 1.2 208v enclosure data, Physical installation 1 - 4 – Yaskawa E7B Drive Bypass User Manual

Page 16

Advertising
background image

Physical Installation 1 - 4

Enclosure Data

Table 1.2 208V Enclosure Data

Input
Volts

HP

1

Drive

Model

CIMR-

Bypass

2

Model

Number

NEC

FLA

OL

110%
1 min

Heat

3

Loss

Watts

Enclosure Dimensions

4

NEMA 1 & NEMA 12 -FVFF

H W D

inches

Weight

5

of

Assembly

Enclosure Dimensions w/Add-on

4

NEMA 1 & NEMA 12-FVFF

H W D

inches

Weight

5

of

Assembly

+Add-on

Box

Electrical

Schematic

208

0.5

E7U22P21

E7B_D002

2.4

2.6

68

29.48 19.06 13.66

Dimension Drawing

6

S-5512

115 lbs

43.35 19.06 13.66

Dimension Drawing

S-5513

156 lbs

E7B-00

0.75

E7U22P21

E7B_D003

3.5

3.8

68

1

E7U22P21

E7B_D004

4.6

5.1

78

2

E7U22P21

E7B_D007

7.5

8.2

110

3

E7U22P21

E7B_D010

10.6

11.7

141

5

E7U23P71

E7B_D016

16.7

18.4

202

7.5

E7U27P51

E7B_D024

24.2

26.6

273

10

E7U27P51

E7B_D030

30.8

33.9

365

127 lbs

164 lbs

15

E7U20111

E7B_D046

46.2

50.8

578

20

E7U20151

E7B_D059

59.4

65.3

653


40.48 25.63 14.66

Dimension Drawing

7

S-5514

208 lbs

55.35 25.63 14.66

Dimension Drawing

S-5515

291 lbs

25

E7U20181

E7B_D074

74.8

82.3

746

30

E7U20221

E7B_D088

88.0

96.8

939

221 lbs

307 lbs

40

E7U20301

E7B_D114

114.0

125.4

1340

50

E7U20370

E7B_D143

143.0

157.3

1523

84.00 25.63 26.25

8

Dimension Drawing

9

S-5525

847 lbs

NOT REQUIRED

60

E7U20450

E7B_D169

169.0

185.9

1762

943 lbs

75

E7U20550

E7B_D211

211.0

232.1

2244

100

E7U20750

E7B_D273

273.0

300.3

3003

1214 lbs

125

E7U20900

E7B_D343

343.0

377.3

3296

1330 lbs

150

E7U21100

E7B_D396

396.0

435.6

4029

1423 lbs

Note 1: Horsepower rating is based on a standard NEMA B 4-pole motor.

Note 2: The underscore position in these model numbers codes for the enclosure type: V = NEMA1, B = NEMA12 FVFF.

Note 3: Heat loss is the amount of heat dissipated by the drive at full load with all standard options available inside the enclosure. Drive heat sink losses are

included in the heat loss data. Heat loss data is for the enclosure without the add-on enclosure.

Note 4: Height dimension (H) excludes the mounting screw tabs. Depth dimension (D) excludes MCP disconnect handle.

Note 5: This data represents the total weight with all possible standard options. Weight could be less depending on the options specified.

Note 6: All standard options are available in this size enclosure except options E (RFI Filter) and K (5% Output Reactor). Options E and K require the add-on

enclosure.

Note 7: All options are available in this size enclosure except E (RFI Filter), R (3% Line Reactor), and K (5% Output Reactor). Only option E combined with

either option R or option K can be installed in the add-on enclosure. Options R and K together require an increase in the size of the E7 Bypass Enclosure.

Contact the factory if all three options are required. Options D (2 Motor “OR”) or A (2 Motor “AND”) for 30 Hp and 40 Hp, or for 75 Hp and 100 Hp, require

the next size enclosure.

Note 8: Heat sink mounted externally varies the depth dimension depending on the drive size. Depth will not exceed dimension shown.

Note 9: All options are available in this size enclosure except options D (2 Motor “OR”) or A (2 Motor “AND”) for 75 Hp and 100 Hp require the next

size enclosure.

Advertising