Fig 5.36 over torque detection, Fig 5.37 under torque detection, Programming 5 - 72 – Yaskawa E7B Drive Bypass User Manual

Page 166

Advertising
background image

Programming 5 - 72

After selecting the proper detection scheme the Torque Detection Level (L6-02) must be specified. If the current level read by
the output current transformers rises above (overtorque) or drops below (undertorque) this level, and remains there for at least
the Torque Detection Time (L6-03), then the Torque Detection Function will change the state of any digital output configured
for Torque Detection (H2-01/H2-02= “B: Trq Det 1 N.O.”, or “17: Trq Det 1 N.C.”).

Fig 5.36 Over Torque Detection

Fig 5.37 Under Torque Detection

Out

pu

t

Curre

n

N

or

m

ally

Ope

n T

orque

Det

ec

tio

n

Di

gi

tal

Ou

tp

ut

t

CLOSED

L6-03

L6-03

L6-02

*

*

* When the output current drops below the Torque Detection Level by
approximately 10% of the Drive’s rated output current the digital output is reset.

Closed
Open

Torque detection level -10%

TIME

C

urr

ent

L6-02

Out

put

Curren

t

Norm

al

ly

Open

T

orque

Det

ec

tio

n Di

gi

ta

l

Out

put

L6-03

L6-03

L6-02

*

* When the output current rises above the Torque Detection Level by
approximately 10% of the Drive’s rated output current the digital output is reset.

*

t

t

Closed

Open

Torque detection level 10%

TIME