Drive nameplate information, Fig 1.2 drive nameplate (example), Bypass unit model numbers – Yaskawa E7B Drive Bypass User Manual

Page 20: Fig 1.3 bypass unit model number, Bypass unit enclosures, Physical installation 1 - 8

Advertising
background image

Physical Installation 1 - 8

Drive Nameplate Information

A nameplate is also attached to the right side of the Drive inside the Bypass enclosure. The following nameplate is an example
for a standard Drive.

Fig 1.2 Drive Nameplate

(Example)

Bypass Unit Model Numbers

The model number on the nameplate of the Bypass unit indicates the enclosure, voltage, Drive rated current and options of the
Bypass unit in alphanumeric codes.

Fig 1.3 Bypass Unit Model Number

Bypass Unit Enclosures

All Bypass units are intended for non-hazardous locations. Various enclosure types are provided to protect against the applica-
tion environmental conditions:

Nema Type 1 Enclosures are constructed for indoor use to provide a degree of protection against incidental contact with
enclosed electrical equipment and falling dust or dirt.

NEMA Type 12 FVFF Enclosures. NEMA provides for both non-ventilated and ventilated NEMA 12 enclosures. When
ventilated, a suffix to the type number defines the ventilation method. A NEMA 12 FVFF enclosure has Forced Ventilation
with inlet air Filter and outlet air Filter. The internal pressure is positive with respect to the ambient pressure. UL does not
recognize NEMA 12 ventilated enclosures, therefore, these enclosures are designated NEMA 1 for UL purposes.

Input Power Specifications

Output Power Specifications

Drive Model Number

Drive Enclosure and
Revision Code

Weight

Serial Number

UL File Number

V

E7

2

0

B

D

BASE NUMBER

OPTIONS

Enclosure

Current

Voltage

208V
230/240V
480V

NEC Rated Amps
(Ex.: “096” = 96A)

A
B

Y

T

0

Touchpad & LED
Touchpad & LCD

0

22mm Operators & LCD

D

2 Motor “OR”

A

2 Motor “AND”

Motor Control

F

None (leave blank)
Fuses

Input Fuses

Input Filter

None (leave blank)

N

Cap Filter

E

RFI Filter

E 7 B

Communications

Not Enabled (leave blank)
EtherNet/IP

L

LonWorks

V

Enable Modbus

3

BACnet

J

Enable METASYS N2

U

Enable APOGEE FLN

M

4-20mA Output

None (leave blank)
4-20 mA Output

S

Speed Pot

None (leave blank)
Speed Pot

P

3-15 PSI Transducer

None (leave blank)
3-15 PSI Transducer

W

Custom Nameplates

None (leave blank)
Custom Nameplates

K

Load Reactor

None (leave blank)
5% Load Reactor

E7BVB096RSL

X

Line Impedance

None (leave blank)
3% Bus Reactor

Z

5% Bus Reactor

R

3% Input Reactor

(1)

(1)

(2)

0

0

0

0

0

0

0

(4)

(4)

(3)

(5)

(3)

(3)

(5)

(6)

(1) 3% and 5% Bus Reactors are only available as an option on base numbers up to E7B_D074, A068, and

B040; larger drives have a Bus Reactor as standard.

NEMA 1

3-Contactor Bypass

NEMA 12

(2) 3% Input Reactor, when combined with the standard Bus Reactor (available on base numbers E7B_D088,

A080, and B052 and above), yields a total of 5% input impedance.

(3) Serial Comm options (J), (L), (U) or (V) cannot be ordered if both (S) and (P) are combined.

(4) 2 Motor “OR” and 2 Motor “AND” options (D) and (A) are only available with 22mm operators option (0).
(5) Options (M) and (S) are not available with options (T) or (Y) - 4-20mA output is standard with options (T) or (Y).
(6) Not available with options (T) or (Y).