Output open-phase, An open-phase occurred at the drive output, Diagnostic & troubleshooting 6 - 7 – Yaskawa E7B Drive Bypass User Manual

Page 187

Advertising
background image

Diagnostic & Troubleshooting 6 - 7

LF

Output Phase Loss

Output Open-phase
An open-phase occurred at the Drive output
This fault is detected when output current
has exceeded 5% imbalance.

There is a broken wire in the
output cable.
There is a broken wire in the
motor winding.
The output terminals were loose.

Check the wiring to the motor.
Check the motor for phase to
ground short.

The motor being used has a

capacity less than 5% of the
Drive’s maximum motor capacity.

Check the motor and Drive
capacity.

Low impedance motor was used. Add additional impedance.

Parameter E2-03 set incorrectly

Adjust E2-03 to a lower value.

LL3

Loss of Load Det 1

Loss of Load Detection 1
Drive output current < L6-02 for more than
the time set in L6-03

Motor is underloaded.

Ensure the values in L6-02 and
L6-03 are appropriate.

Check application/machine
status to eliminate fault.

OC

Over Current

Overcurrent
Drive output current exceeded the
overcurrent detection level (approximately
180% of Drive rated output current).

Shorted Drive output phase to
phase, shorted motor, locked
rotor, load too heavy, accel/
decel time too short, contactor
on the Drive output is opened
and closed, a special motor or
a motor with a FLA rating
larger than Drive rated output
current.

Remove the motor and run the
Drive without the motor.

Check the motor for a phase-to-
phase short.

Check the Drive for a phase-to-
phase short at the output.

Verify C1-01 and C1-02 are set
correctly.

Check load conditions.

OH1

Heatsnk MAX Temp

Cooling Fin/Cooling Fin Fan Overheat
The temperature of the Drive cooling fin

exceeded the temperature programmed in
parameter L8-02, and L8-03=0-2.

Cooling fan(s) are not
working, high ambient
temperature, a heat source is
too close to the Drive.

Check for dirt build-up on the
fans and cooling fins.

Reduce the ambient temperature
around the Drive.

Drive Internal Cooling Fan

Remove the heating unit/Replace
the cooling fan.

OH3

Motor Overheat 1

Motor Overheating Alarm
The Drive stops or continues operation
according to the setting of L1-03.

Overheating of motor as
measured by motor thermistor.

Recheck the cycle time and the
size of the load.

Recheck the accel/decel time
(C1-01 and C1-02).

Recheck the V/F pattern (E1-01
thru E1-13).

Recheck the motor rated current
value (E2-01).

OH4

Motor Overheat 2

Motor Overheating Fault
The Drive stops operation according to the
setting of L1-04.

Overheating of motor as
measured by motor thermistor.

Recheck the cycle time and the
size of the load.

Recheck the accel/decel time
(C1-01 and C1-02).

Recheck the V/F pattern (E1-01
thru E1-13).

Recheck the motor rated current
value (E2-01).

Table 6.1 Fault Displays and Processing

Digital

Operator Display

Description

Cause

Corrective Action