Table 1.3 240/230v enclosure data, Physical installation 1 - 5 – Yaskawa E7B Drive Bypass User Manual
Page 17

Physical Installation 1 - 5
Table 1.3 240/230V Enclosure Data
Input
Volts
HP
1
Drive
Model
CIMR-
Bypass
2
Model
Number
NEC
FLA
OL
110%
1 min
Heat
3
Loss
Watts
Enclosure Dimensions
4
NEMA 1 & NEMA 12 -FVFF
H W D
inches
Weight
5
of
Assembly
Enclosure Dimensions w/Add-on
4
NEMA 1 & NEMA 12-FVFF
H W D
inches
Weight
5
of
Assembly
+Add-on
Box
Electrical
Schematic
240
0.5
E7U22P21
E7B_A002
2.2
2.4
68
29.48 19.06 13.66
Dimension Drawing
6
S-5512
115 lbs
43.35 19.06 13.66
Dimension Drawing
S-5513
156 lbs
E7B-00
0.75
E7U22P21
E7B_A003
3.2
3.5
68
1
E7U22P21
E7B_A004
4.0
4.4
78
2
E7U22P21
E7B_A006
6.8
7.5
110
3
E7U22P21
E7B_A009
9.6
10.6
141
5
E7U23P71
E7B_A015
15.2
16.7
202
7.5
E7U25P51
E7B_A022
22.0
24.2
273
10
E7U27P51
E7B_A028
28.0
30.8
365
127 lbs
164 lbs
15
E7U20111
E7B_A042
42.0
46.2
578
20
E7U20151
E7B_A054
54.0
59.4
653
40.48 25.63 14.66
Dimension Drawing
7
S-5514
208 lbs
55.35 25.63 14.66
Dimension Drawing
S-5515
291 lbs
25
E7U20181
E7B_A068
68.0
74.8
746
30
E7U20221
E7B_A080
80.0
88.0
939
221 lbs
307 lbs
40
E7U20301
E7B_A104
104.0
114.4
1340
230
50
E7U20370
E7B_A130
130.0
143.0
1523
84.00 25.63 26.25
8
Dimension Drawing
9
S-5525
847 lbs
NOT REQUIRED
60
E7U20370
E7B_A154
154.0
169.4
1544
943 lbs
75
E7U20450
E7B_A192
192.0
211.2
1860
100
E7U20750
E7B_A248
248.0
272.8
3003
1214 lbs
125
E7U20750
E7B_A312
312.0
343.2
3045
1330 lbs
150
E7U20900
E7B_A360
360.0
396.0
3440
1423 lbs
Note 1: Horsepower rating is based on a standard NEMA B 4-pole motor.
Note 2: The underscore position in these model numbers codes for the enclosure type: V = NEMA1, B = NEMA12 FVFF.
Note 3: Heat loss is the amount of heat dissipated by the drive at full load with all standard options available inside the enclosure. Drive heat sink losses are
included in the heat loss data. Heat loss data is for the enclosure without the add-on enclosure.
Note 4: Height dimension (H) excludes the mounting screw tabs. Depth dimension (D) excludes MCP disconnect handle.
Note 5: This data represents the total weight with all possible standard options. Weight could be less depending on the options specified.
Note 6: All standard options are available in this size enclosure except options E (RFI Filter) and K (5% Output Reactor). Options E and K require the add-on
enclosure.
Note 7: All options are available in this size enclosure except E (RFI Filter), R (3% Line Reactor), and K (5% Output Reactor). Only option E combined with
either option R or option K can be installed in the add-on enclosure. Options R and K together require an increase in the size of the E7 Bypass Enclosure.
Contact the factory if all three options are required. Option A (2 Motor “AND”) for 30 Hp and 40 Hp, or for 75 Hp and 100 Hp, require the next size
enclosure. Option D (2 Motor “OR”) for 40 Hp, or for 75 Hp and 100 Hp, require the next size enclosure.
Note 8: Heat sink mounted externally varies the depth dimension depending on the drive size. Depth will not exceed dimension shown.
Note 9: All options are available in this size enclosure except options D (2 Motor “OR”) or A (2 Motor “AND”) for 75 Hp and 100 Hp require the next size
enclosure.