General peripheral devices, Magnetic contactor, Ac and dc reactor – Yaskawa E7B Drive Bypass User Manual

Page 290: Fig e.1 connected drive (kva), Noise filter

Advertising
background image

Peripheral Devices E - 4

General Peripheral Devices

The following peripheral devices may be required to be mounted between the AC main circuit power supply and the Drive
input terminals R/L1, S/L2, and T/L3.

For more details on peripheral devices, contact the manufacturer.

Magnetic Contactor

Mount a surge protector on the coil. When using a magnetic contactor to start and stop the Drive, do not exceed one start per
hour.

AC and DC reactor

Install a reactor to connect to a power supply transformer of large capacity (600 kVA or more) or to improve the power factor
on the power supply side.

Fig E.1 Connected Drive (kVA)

Noise filter

Use a noise filter exclusively for the Drive if radio noise generated from the Drive causes other control devices to malfunction.

CAUTION

Never connect a general LC/RC noise filter to the DriveDrive output circuit.
Never connect a phase-advancing capacitor to the input or output sides, or a surge suppressor to the output
side of the Drive. When magnetic contactor is installed between the Drive and the motor, never turn it on or off
during operation.

4000

P

ower Supply (kV

A)

600

0

60

400

AC or DC

Reactor Not Required

AC or DC

Reactor Required

Advertising