5.4.2 MicroLogix 1500 Fault LED

The faultless communication state is reached, if the Fault LED of the MicroLogix Controller
is in off state.

If there is a problem with the expansion module the Fault LED is flashing red. Then go
online with your RSLogix 500 project and open up the processor status dialog and check the
error tab for the fault reason.

5.4.3 SYS and COM Status LEDs

This PS69-DPM module has two bicolor status LEDs. They inform the user about the
communication state of the module. The SYS LED shows the common system status of the
card. It can be yellow or green. The COM LED displays the status of the PROFIBUS
communication. It can flash green or red. The meaning of the LEDs is described in the
booklet that came with the System Software CD and in CompactLogix I/O LED (page 100).

If the SYS LED is solid green and the COM-LED static green, the card is in cyclic data
exchange with the connected Slaves and the communication is running with out fault.

5.4.4 Error Sources and Reasons

This chapter describes typical problems, error sources and questions that come up while
commissioning the PROFIBUS-DP master module PS69-DPM. The following table
summarizes the typical error sources and gives a hint of possible reasons for the problem.

Behavior

Significance

Typical Reason

Help

CompactLogix
I/O LED is Green

flashing

No communication with the
PS69 module (or other

modules)

Modules slot number in
RSLogix program does not
match with the physical slot of

the module
Configured Input / Output size

is wrong

Check modules slot number in
RSLogix project
Compare configured Input /
Output size with required

values

MicroLogix
Fault LED is flashing

Red

No communication with the
PS69 module (or other
modules)

Modules slot number in
RSLogix program does not
match with the physical slot of

the module
Configured Vendor ID / Module
ID / Input / Output /
Configuration array size is

wrong

Check modules slot number in

RSLogix project
Compare configured Input /
Output size / Vendor ID

/Module ID with required values

PS69-DPM
COM LED is off
SYS LED Flashing

irregular green

Configuration missing or faulty No configuration stored

Download a Configuration to
the card with PROSOFT.fdt

(SYCON.net)

PS69-DPM
COM LED is static
green and SYS LED
flashing cyclic fast

green

Application is not ready

PLC is not in RUN Mode.
PLC application has set the

NRDY bit.
PLC has no I/O communication

with the module

Bring PLC into RUN Mode.
Check that the PLC application

has deleted the NRDY bit.
Check PLC’s I/O LED