GLOBAL-BITS

Bit Offset

Member Name

Data Type

Signification

Meaning if Bit is set

0

Ctrl

BOOL

CONTROL-ERROR Parameterization error

1

Aclr

BOOL

AUTO-CLEAR-
ERROR

Module stopped communication
with all slaves and reached the

auto-clear-end state.

2

Nexc

BOOL

NON-EXCHANGE-
ERROR

At least one slave has not reached
the data exchange state and no

process data will be exchanged.

3

Fat

BOOL

FATAL-ERROR

Because of major bus error, no
further bus communication is

possible.

4

Eve

BOOL

EVENT-ERROR

The module has detected bus short
circuits. The number of detected
events is contained in the
Bus_error_cnt variable. This bit is
set when the first event was

detected and will remain set.

5

NRdy

BOOL

HOST-NOT-
READY-

NOTIFICATION

Indicates if the Application program
has set its state to operative or not.
If this bit is set the Application
program is not ready to

communicate

6

Tout

BOOL

TIMEOUT-ERROR The module has detected an

overstepped timeout supervision
value because of rejected
PROFIBUS telegrams. It is an
indication for bus short circuits
while the master interrupts the
communication. The number of
detected timeouts is available in
the Time_out_cnt variable. This bit
will be set when the first timeout is

detected and will remain set.

7

Reserved1

BOOL

Reserved

Reserved

ERROR-EVENT Codes for an Err_Rem_adr of 255

Code

Indication

Source

Corrective Action

0

No errors

None

None.

50

USR_INTF-Task Not Found

Master

Firmware is invalid. Module must be
updated.

51

No Global Data

Master

Firmware is invalid. Module must be

updated.

52

FDL-Task Not Found

Master

Firmware is invalid. Module must be
updated.

53

PLC-Task Not Found

Master

Firmware is invalid. Module must be
updated.

54

Non Existing Master Parameters

Master

Execute download of configuration

database again.

55

Faulty Parameter Value in the
Master Parameters

Configuration

Firmware is invalid. Module must be
updated.

Advertising