PS69-DPM ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 97 of 130

October 1, 2014

5.2.3 PS69 LEDs

The LEDs as shown on the front panel will be used to indicate status information of the
PS69-DPM Master module. Each LED has a specific function during Run, configuration
download, and error indications. The following table shows the reaction of each during these
states for Master and Slave.

LED

Color

State

Description

SYS

Yellow

Flashing cyclic at
1Hz

Device is in boot loader mode and is waiting for firmware
download.

Yellow

Flashing cyclic at

5Hz

Firmware download is in progress.

Yellow

Flashing irregular (*) Hardware or runtime error detected.

Green

Static On

Communication is running. The device has established at
least one configured fieldbus connection.

Green

Flashing cyclic at
5Hz

No error in configuration found, communication is stopped.

Green

Flashing irregular (*) Power Up: Configuration missing or faulty, device needs

commissioning.
Runtime: Host Watchdog timeout

Off

Off

Device has no power supply or hardware defect.

COM

Green

On

Device is holding the PROFIBUS token and is able to transmit
telegrams.

Green

Flashing acyclic (**)

Device is sharing the PROFIBUS token with other master

devices in the PROFIBUS network.

Red

On

Device has found a communication problem to at least one
PROFIBUS-DP slave device or has detected a short circuit.

Off

Off

Device is not configured or has not received the Token
permission on the PROFIBUS network.

(*) 3 times fast at 5 Hz, 8 times between 0,5Hz and 1Hz
(**) between 0,5Hz and 100Hz