PS69-DPM ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 41 of 130

October 1, 2014

Station Table

Note: The following illustration shows how to change the bus address for a Slave. This dialog box is the only
place that allows you to change the slave address.

Complete the process click the OK or Apply button and close the dialog box. The Master
settings are now complete.

Note: The slave offset addresses shown here are not the same you will find in the PLC memory. You have to

add 44 words the Input address (to allow space for the Status Information area) and 8 words to the Output
address (to allow space for the Command Information area). See IO Arrays Overview for details.