Contents

PS69-DPM ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 66 of 130

ProSoft Technology, Inc.

October 1, 2014

Code

Indication

Source

Corrective Action

18

Master not in Logical Token Ring

Master

Check FDL-Address of master or highest-
station-address of other master systems.

Examine bus cabling for bus short circuits.

21

Faulty Parameter in Request

Master Telegram

Master has a firmware issue.

Slave Diagnostics Field

The Slave Diagnostics array is an array of 8 bytes which includes slave diagnostic
information based on the settings used to execute this command. The definition of this array
and its indications are shown in the Following table.

Note: The same Slave Diagnostic function can also be executed by CIP message functionality described later in

this manual. Some types of the CompactLogix controller family do not support messaging. This method below
can be used for controllers that only support I/O or I/O and CIP messaging. The slave diagnostic via I/O has the

limitation that it cannot show extended diagnostic information, if a slave supports this. It can only give the

mandatory diagnostic information of a slave. Extended diagnostic information can be received with the CIP

message functionality only.

Byte Offset

Structure member

Data Type

Description

72

Slave Address

SINT

Address of Slave with the Diagnostic request

73

Slave Diag Failure

SINT

See Definition Below

74

Station Status_1

SINT

See Definition Below

75

Station Status_2

SINT

See Definition Below

76

Station Status_3

SINT

See Definition Below

77

Master Address

SINT

This byte contains the master address of the PROFIBUS-
DP master which has done the parameterization of the

slave. If a slave is not parameterized the value is 255

78 to 79

Ident Number

INT

PROFIBUS Ident number from Slave in which the
diagnostic request was made

Slave Diag Failure
This byte reflects the status of the DDLM_DIAG request. See table below for possible error
codes.

Error Code

Significance

Error source

Help

0

Service could be executed
without an error

No error

-

17

No response from the station

SLAVE

Check network wiring, check bus address of
slave or baud rate support

18

Master not into the logical

token ring

Network in general

Check master DP-Address or highest-station-
address of the Master. Examine bus wiring for

bus short circuits

161

Remote Address in request
service out of range

APPLICA-TION

Check address parameter in diag request